Testing a metal-enclosed bus system 32/955
       Table 32.1(A)  For series I voltage systems: Insulation levels, power frequency and impulse withstand voltages for metal-enclosed
       bus systems
       Nominal system   Rated max. system   One-minute power frequency voltage withstand   Standard lightning impulse,
       voltage        voltage       at a frequency between 45 and 65 Hz for LT and   1.2/50 p voltage withstand
                                    25 and 100 Hz for HT systems             (phase to ground)
       1              2             3                    4                   5
                                    For a switchgear   For the tap-offs in a   (a)  We consider here only
                                    assembly and a bus   power-generating station,   List 11, which is more
                                    system           connecting a UAT through   prevalent. For List I,
                                    (phase to ground)   the main bus section between   refer to Table 13.2.
                                                     the generator and the   (b) For impulse voltage
                                                     generator transformer      withstand across the contact
                                                     (Figure 31.1) (phase to    gaps of an interrupting
                                                     ground)                    device refer to
                                                                                IEC 60694
       kV (r.m.s.)    kV (r.m.s.)   kV (r.m.s.)      kV (rms.)               kV (peak)
        0.415          0.44          2.5             -                       -
        0.6            0.66          2.5             -                       -
        3.3            3.6          10               21                       40
        6.6            7.2          20               27                       60
       11             12            28               35                       75
       15             17.5          38               -                        95
       22             24            50               55                       125
       33             36            70               75                       170
       Based on IEC 60439-2 LT, IEC 60694 for HT and IS 8084 for tap-offs.
       Notes
       1  Generally, there is no application of a bus system beyond a maximum system voltage of 36 kV.
       2  Field tests (power frequency voltage withstand) after erection at site, if required, may be conducted at 85% of the values indicated above
          in LT and 80% in HT systems.





       Table 32.1(8)  For series I voltage systems: Power frequency voltage withstand levels for metal-enclosed bus systems
       Nominal system   Rated maximum   One-minute power frequency   Field test after erection at site (phase to ground)
       voltage      system voltage   withstand voltage at any
       v,                           frequency between 25 and   A.C. test lfor one minute at any   D. C tesP
                                    100 Hz (phase to ground)   frequency between 25 and  100 Hz)
       I            2               3                          4                           5
       kV (mu.)     kV (r.m.s.)     kV (r.m.s.)                kV (rms.)                   kV

        0.415        0.44            2.0                        2.0                        3.0
        0.6          0.66            2.0                        2.0                        3.0
        3.3          3.6             9.5                        8.6                        5.0
        6.6          7.2             17.0                      15.2                        10.5
       11            12             27.0                       24.0                        18.0
       15            17.5           36.0                       32.0                        25.0
       22           24              52.0                       46.0                        37.5
       33           36              76.0                       68.0                        60.0
                                                               (2V, + 2) for HT systems

       Based on BS 159
       * In the absence of a.c. test voltage at site, a d.c. test can also be conducted, the duration of which will be  15 minutes.