Page 1012 - Industrial Power Engineering and Applications Handbook
P. 1012

Testing a metal-enclosed bus system  32/957
       Effect of solar radiation                     32.3.7  Verification of protective circuits
       The effect of  solar radiation  must  be considered in  the   All the protective circuits will be checked for continuity
       outdoor part  of  a  bus enclosure exposed  to  solar heat.   and operational requirements.
       This  effect  may  be  observed  for all  LT  and  HT  bus
       enclosures, as all are influenced equally by such radiations,   32.3.8  Verification of clearance and creepage
       particularly IPB enclosures, as discussed in Section 3 I .4.4.   distances

       32.3.5  Verification of short-circuit strength   The clearance will be verified as in Table 28.4 while for
                                                     creepages Table 28.5 may be followed.
       For straight lengths and tap-offs
                                                     32.3.9  Verification of degree of protection
       The test procedure is generally the same as that discussed
       for switchgear assemblies (Section  14.3.6).  It is carried   Enclosure test
       out on a similar section to that used for the temperature
       rise  test  and the  power  supply can be  single-phase or   The types of  protection and their  degree  are generally
       three-phase. If three-phase, the bus conductors are shorted   the  same as those defined for motors  in  Section  1.15.
       at  one end while  the  other ends are connected to the   Tables I. 10 and I. 1 I. The test requirements and methods
       power source. If a single-phase power is used, the circuit   of conducting such tests are also almost the same as for
       should be so arranged that the current flows through the   those motors, discussed in Section 1 1 S.3.
       two adjacent phase conductors. The force due to a three-
       phase  fault  would  be  approximately  86.6%  of  this.   Watertightness test
       Therefore, for single-phase  tests,  the current would be
       zix6.6 or approximately 93% of that prescribed in Table   This test  is applicable  to  all  outdoor parts  of  any  bus
       13.10. The test  results  should show  no sign of  undue   system and on both indoor and outdoor parts of an isolated
       deformation.  Slight deformation  may  be  acceptable,   phase  bus  (IPB)  system.  Each  enclosure  to  be  tested
       provided that the clearance and the creepage distances   (such as the enclosure of one phase in an isolated phase
       are complied with  and the  degree of  protection  is  not   bus system) should be complete in all respects with all
       impaired. The insulation and mounting supports, however,   its fittings and mounts in place. The length of the testpiece
       must show no signs of deterioration.          must be the same as that considered for the temperature
                                                     rise test (Section 32.3.4).
                                                       As ANSI C-37120C and IS 8084 water under a head of
       For the tap-08s in a power-generating station,   1 1 m through a hose of 25 mm diameter held at 3 m from
       connecting a  UAT through the main bus section   the enclosure will be impinged at an angle of at least 45"
       between the generator and the generator       from the horizontal on all sides and the entire length of
       transformer                                   the enclosure for a period of 5 minutes. No water should
                                                     enter the enclosure.
       As discussed in Section 13.4.1(5), these sections are under
       the cumulative influence of two power sources and may
       be tested for a higher short-time rating, which would be   Air leakage test
       the  algebraic  sum  of  the  two  fault  levels,  one of  the   This test is  prescribed by  ANSI C-37/20C  for isolated
       generator and the other of the generator transformer as   phase  bus  systems  after  they  have  been  assembled  at
       noted in Table  13.8. Also refer to Figures 3 1. I  and 13.18   site. The test is conducted by  filling the enclosure with
       for more clarity.                             air up to a pressure of 15 cm of water (1 500 N/m').  After
                                                     the air supply is shut off, the pressure must not drop to
       For the ground bus                            less than 7.5 cm of  water in  15 seconds. All  breathers
                                                     and drain holes must be sealed before the test.
       In  an  isolated phase  bus  (IPB) system, the ground  bus
       must be capable of carrying the same short-time current
       as  for  the  main  conductors for  2  seconds,  for  both   32.3.10  Measurement of resistance and
       discontinuous and continuous grounding systems.      reactance
                                                     The mean values of the resistance and reactance per phase
       32.3.6  Verification of momentary peak or     are determined on at least two trunking units.  including
             dynamic current                         the joints, from a total  length of 6 m. If the total length
       The test  method  and test  results  will  generally  be the   of  the bus  section is less than this,  the  values may  be
       same as for a switchgear assembly. discussed in Section   dctcrmined on the entire length of the bus system.
                                                       If  Vdt, Vd2 and Vd, are the voltage drops in the three
       14.3.7.                                       phases, then the average voltage drop
         For the tap-offs,  connecting a UAT through the main
       bus  section  between  the  generator  and  the  generator   'dl
       transformer. however, as discussed above, the momentary   Vd =   vd2 + vd3  volts per phase and
                                                                 3
       peak  current will depend upon the short-time rating of         I,  +I,  +I,  Amps per phase
       such tap-offs. The likely ratings are noted in Table 13.8.   average current  I,,  =
                                                                            3
   1007   1008   1009   1010   1011   1012   1013   1014   1015   1016   1017