Page 509 - Industrial Power Engineering and Applications Handbook
P. 509

Instrument and control transformers:  application  and selection  151483
               R        Y        B    N
               I        I        I    I    Stabilizing
                                           resistors
                                           (1450 R  each
                                           for example 15.6)
                                           Non-linear
                                           resistors






          Figure 15.27  Three-element high-impedance circulating
          current relay scheme

          maximum value of the stabilizing resistance to be supplied
          will depend upon the type of protection (ground or phase
          or both)  and  the  relay  setting.  Generally,  it  may  vary
          from SO to  IS00 Q.
          Fault within the protected zone
          Refer to Figure 15.28(a). The balance of the two sets of
          CTs  is  disturbed  again.  The  CTs  now  have  the  same
          polarity and currents as the two sets add up to cause a   High impedance differential protection
          high-imbalance spill current through the relay. Referring   relay. It operates for the fault occurring
                                                                 within the protection zone
          to Figure  15.28(b),                                   Fault current through ground for fault
                                                                 on phase B
          I,,  = I,, + 12 = (1\P - I,,,?)   These are all phasor
                                 quantities, but considered             (a) Power circuit
                        1
              + (I,,,  ~  I,,,   linear, for ease of
                                 illustration  and without
             = 142 + I,,,  - 21,n   1 much error
            The additive characteristic of the scheme now has high
          stability and prevents the relay from operating on moderate
          external faults, while it is sensitive to small spill currents
          for all internal ground and phase faults, including winding   FIL-/
          faults.
          2 Current setting of the relay
          The  relay  has  voltage  as well  as current  settings. The
          former defines the stability limit against through-faults,
          as  discussed  above,  while  the  latter  determines  the
          sensitivity of the protected zone.
          If  IPf = minimum  fault  current  through  the  primary
                (chosen on the basis of the rated full-load current
                of  the  machine  or the  system  being  protected)                      Differential
                required  to trip the relay.  It  may be termed the                      relay
                minimum  primary  operating  current  (POC)  of
                the scheme. Ipf, In terms of the secondary
              = n x I,f
             IZ = turn ratio of the CTs
            I,,  = corresponding to the V,,  to account for the most
                severe through-fault
            I,,  = relay current setting, i.e.  minimum spill current
                required to operate the relay
                                                                   I
          Then                                                     L2     4,  = IC2  + 41
          -    -   -                                                   (b) Control scheme
          I,,  = I,,  + I,,
          Since on  a  fault  the  p.f. is  low  (Section  13.4.1(5))  all   Figure 15.28  Fault within the protected zone
   504   505   506   507   508   509   510   511   512   513   514