Page 514 - Industrial Power Engineering and Applications Handbook
P. 514

15/488  Industrial Power Engineering and Applications Handbook

                                                                          Rr =s
                                                                               1
                 I          Knee ooint            I    Relay resistance,
                                                                            = 100 R
                                                       (for the same relay as in the earlier example)
                                                       :.  Required stabilizing resistance,
                                                       R,t  = 1550 - 100 = 1450 R
                                                       4 Peak voltage across the relay circuit
                                                           Vk  = 310 V
                                                           V,  = is,  R,
                                                             = 13.3 x 1550
                                                             = 20,615 V
                          Excitation current lm (mA) -   :.   V,  =  27/1,/310(20,615 - 310)
                                                             = 7095 V
                 0    20   I,   1.51,
                       (Ampere-turns converted into Amps.)   which is more than 3 kV. Hence, a non-linear resistance will
                                                       be necessary across the relay branch and must be ordered
                                                       from the manufacturer with the relay.
         Figure 15.33  Assumed magnetizing characteristic of 3000/ 1 A
        class PS CTs                                   5 Specification for class PS CTs
                                                       CTs : 33 kV
         For all the CTs let R,,  = 10 R and lead resistance
                                                       CTR = 1000/1 A   Qty 3 numbers
         Ri  = 0.75 x 2  = 1.5 R
                                                       CTs : 11 kV
        The fault level of the system
                                                       CTR = 3000/1 A   Qty 21  numbers
               750
         Is,  =   1.732 x 11                             Vk  2 310 V
                                                         I,  = as low as possible, but not more than 20 mA at 155
           = 39 (say 40 kA)                                  V. The CT manufacturer must provide the magnetizing
         and in terms of the secondary                       characteristics.
         is,  =  40 x -                                Notes
                 lo3
                     xl
                 3000                                  1  In the  above case the  incoming feeder would trip,  even
           = 13.3 A                                      when the fault occurs in any of the outgoing feeders, which
                                                         may not be desirable.  It is therefore  recommended that
         1 Relay voltage setting (stability limit)       this  scheme  be  applied to  individual feeders,  so that  in
         V,, = 13.3 (1 0 + 1.5) (considering the resistance at the operating   case of  a fault, only the faulty feeder is isolated rather than
            temperature)                                 the whole system.
           = 152.95 V                                  2  With the relay one should also order from the manufacturer
         say, 155 V or nearest higher setting available on the relay.   (a)  Stabilizing resistance of  1450 R and
                                                         (b)  A non-linear resistance to discharge the excess induced
         :.  Minimum kpv,  V, = 2 x  155                    e.m.f., across the relay circuit.
                                                         Both these resistances are illustrated in Figure 15.27.
                        = 310 V (Figure 15.33)
         2 Relay current setting.                      15.6.7  Core-balanced current transformers
                                                             (CBCTs)
                   Ipf  656.25 A
                     =
            I,,,  at  155 V =  20 mA from the curve of  Figure 15.33   These are protection CTs and are used for ground leakage
                                                       protection. They are also a form of summation CTs, where
         ..    656.25 =  3000 (7 x 0.02 + Ist)         the phasor sum of the three phase currents is measured.
         or        ISt =  656.25 -7  x 0.02            The phasor difference, if any, is the measure of a ground
                                                       leakage in the circuit. They are discussed in Section 21.5.
                        3000
                     =  0.0788A
         Therefore, the relay can be set, say, at  10% of  1 A.   15.7  Short-time rating and effect of
          The scheme is suitable to detect both a ground fault and
         a phase fault.                                      momentary peak or dynamic
         3 Stabilizing resistance                            currents
         Relay circuit impedance, R,  = -
                               155
                               0.1                     The normal practice of users when selecting a measuring
                              = 1550 R                 or a protection CT has been to specify only the current
   509   510   511   512   513   514   515   516   517   518   519