Page 515 - Industrial Power Engineering and Applications Handbook
P. 515

Instrument and control transformers: application and selection  15/489
       ratio and the likely maximum VA burden it may have to   Table 15.11  Maximum short-time factors obtainable
       feed as well as the class of  accuracy for metering  and   economically corresponding to rated output, accuracy class,
       accuracy limit factor.                         accuracy limit factor and rated short-time for wound primary
                                                      current transformers
        Fault level is normally not mentioned, nor is it requested
       by the CT manufacturer. Generally, it should be sufficient
       to meet the likely fault level of the system and its duration   Accuracy   Rated output  STF obtainable, corresponding to the
                                                                          rated short times  up to
                                                      class
                                                                VA
       in most cases, particularly on an LT system. For critical
       installations, large feeders and all HT systems, however,          0.5 s     1.0 s     3.0 s
       it is recommended to check the suitability of the CTs for
       the system fault level and its duration.       (A) Measuring CTs
        A short-circuit on a system will cause overheating as   0.5   2.5   1100    115       450
       a result of the short-time current, Isc, and its duration of   5   750       525       300
       1 or  3 seconds, according  to the  system requirements   10       500       350       200
      and  its  protective  scheme.  It  will  also  develop    15        315       215       150
                                                                                               15
                                                                          200
                                                                                    125
      electrodynamic forces (equation (28.4)) as a result of the   1   30   1100    775       450
                                                                2.5
      momentary first peak of the fault current (in CTs it is 2.5   5     1000      700       400
      times the short-time current, Isc, as in IEC 60044-1; see   10      675       415       275
       also Table 13.11). These forces may result in electrical   15      500       350       200
       as well as mechanical damage to the windings of a CT   3   30      215       200        110
      depending  upon  the  number  of  turns  in  the  primary   2.5     1100      115       450
      winding and the configuration of the coil. For bar primary   5      1000      100       400
       CTs, having only one turn in the primary, such forces are   10     675       475       215
                                                                                              200
                                                                                    350
                                                                15
                                                                          500
      the least, hence the statement above. With a lower class   30       215       200        110
       of accuracy, a low VA level, and a lower accuracy limit
      factor (for protection CTs) a CT can easily be built to be   (B) Protection CTs
       mechanically rugged.  But higher requirements  of  such   5P 10   2.5   550   400      225
                                                                5
      parameters may necessitate a bulky CT, disproportionate   10        375       275       150
                                                                                    150
                                                                          225
                                                                                               90
       in size and cumbersome to install.                      15         150       100        60
        In  most applications,  a bar  primary  CT is generally   30        -        -          -
      used and a normal CT may be suitable. But for too small   5P15   2.5   325    250       135
      ratings,  where  the  use  of  a  wound  primary  CT  is   5        215       200       110
      imperative, short-circuit effects must be considered, except   10   150       100        60
      the CTs for an LT system, where the fault level for such   15        85        60        35
                                                                            -
                                                                                                -
                                                                                     -
      small ratings may be very low and may not matter (Section   5P20   30   325   250       135
                                                                2.5
       13.4.1(5)). For applications  on an HT system, where a   5         200       125        15
      wound primary CT is imperative, choice of  a CT from     10         100        75        40
      standard wound primary CTs may still be possible, meeting   15        -        -          -
      the minimum requirements of class of accuracy,  VA burden   30        -        -          -
      and short-time rating. IEC 60044-1 indicates for measuring   10P5   2.5   1000   700    400
      and protection CTs the maximum short-time factors (STF)   5         750       525       300
      that can be obtained economically  for a normal wound    10         425       300       175
                                                               15
      primary CT where                                         30         375       215       150
                                                                                    100
                                                                                               60
                                                                          150
                                                                          600
      Short-time factor (STF)  =  Rated short-time current   lOPl0   2.5   425      425       250
                                                                                    300
                                                                                              175
                                                                5
                             Rated primary current
                                                               10         215       200       110
                                                               15         200       125        15
                            Is,
                          --                                   30           -        -          -
                          -
                            I,                        10P20     2.5       325       225       125
      Some STFs for more important  CTs are reproduced  in      5         215       200       110
      Table 15.11.                                             10         125        75        50
                                                               15          85        60        35
                                                               30           -        -          -
      Example 15.7
      Consider a 1.5 MVA 33/11 kV transformer having a fault level
      of  750  MVA. The  STF can  be calculated as  below with a
      circuit of  11 kV:                              :.   STF=   40 x  1000
                750                                              79
          Isc  =   ~                                        = 506
               ax 11
            = 40 kA                                   Consider a CT with a ratio of  100/5 A and select a bar
      and  I,=   ~   1.5   x  1000                    primary CT. If a bar primary is not practicable, then for
               ax 11                                  an  STF of  almost  500,  we  can  choose  a  wound-type
              79A                                     measuring CT from Table 15.11 with an accuracy class
   510   511   512   513   514   515   516   517   518   519   520