Page 517 - Industrial Power Engineering and Applications Handbook
P. 517

Instrument and control transformers: application and selection  15/491
                                                       4  One should select a lower secondary current, say, 1 A
                                                          CT, for installations requiring long lengths of connec-
                                                          ting leads, such as for remote measurement of current
                                                          or other quantities. It is advisable to limit  the extra
                                                          VA  burden on the CTs, on account of such leads.
                                               **
                                               0.3 R
                                                              SECTION 111:  TESTING OF
                                                            INSTRUMENT AND CONTROL
                                                                   TRANSFORMERS
                         I
                     Excitation circuit
                 *Typical parameters of the CT         15.1 0 Test requirements
                **
                  Resistance of instruments of 7 5VA
           (a) Under energized and closed circuit condition   The following tests are recommended on a finished voltage
                                                         current transformer:
                       --  -
            Z, = 103 23 kQ   -     1.0R                   Type tests  These are conducted on a finished voltage
                     393 7A        u                      or current transformer, one of each design and type,
                                                          to verify  their  compliance with the design  data and
                                                          relevant Standards.
                                                          Routine tests  These are conducted on each finished
                                                          voltage or current transformer to verify their suitability
                                                          for the required duty.
                                                          Field tests
                                                          Special tests  Any tests that are not  covered above
                                                          and are considered necessary by the user may be agreed
                                                          upon  between the manufacturer and the user.
              * Approx. impedance of the excitation circuit.
             (b) Under energized but open circuit condition.
                                                       15.10.1  Voltage transformers
              CT circuit referred to the Secondary side.
                                                        1  Type tests  These will cover the following tests:
                                                          (i)  Temperature rise test
                                                          (ii)  Verification of dielectric properties on the primary
                                                             windings;  To  check  the  insulation  level,  as  in
         likely that the induced voltage across the CT open terminals   Tables 13.2 and 14.3 for series IandTables 14.1
         may give a further momentary kick upto 242 times the voltage   and  14.2 for series I1 voltage systems.
         calculated above, as the current and hence the voltage shall
         undergo a rapid change from one peak to the other  within   (a)  Power frequency voltage withstand or HV
         one half of a cycle, Section  1.2.1.                    test.
                                                             (b)  Impulse  voltage  withstand  or  lightning
         3  Provision  must  be  made  to  short-circuit  all  the  CT   impulse test for system voltages 2.4 kV and
           secondary terminals not in use (for example, in three   above.
           energized  measuring  CTs,  connected to  a  common    Since a VT is associated with a switchgear,
           ammeter through a selector switch, when either none   either  with  its  assembly  or  with  the
           or any one of the CTs only may be connected to the     switchyard. the above two tests are almost
           ammeter at  a  time,  the  other  CTs remaining  out of   the same asthoseforthe switchgear assembly
           circuit). In such cases, except for the CT in use, the   and  as  discussed  in  Chapter  14. The  test
           remaining CTs should be shorted. The selector switches   requirements and procedure are also similar.
           are therefore designed so that all the CT terminals not   (iii) Wet  test  for  outdoor  type  transformers   The
           in use are shorted automatically through the switch,   outdoor VTs are also tested for dielectric properties
           even during a change-over from one CT to another. A   under  wet  conditions. The procedure  to  create
           typical circuit diagram of the switch is shown in Figure   the wet conditions  and to carry out the test  are
           15.34, which illustrates the fulfilment of this require-   specified in IEC 60060-2. In wet conditions, the
           ment. It may be observed that in the OFF position, all   VT has the same test voltages as specified above.
           the CT secondaries are shorted and when any one of   (iv) Verification of accuracy   The test results obtained
           them  is  in  circuit,  the  remaining  two  are  shorted.   must comply with the values of Tables 15.5 and
           All  such switches must  be the  ‘make before  break-   15.6 for a measuring and a protection transformer
           type’,  so  that  the  CT  terminals  are  shorted  before   respectively.  For  brevity,  we  have  limited  our
           being  connected  to  the  load  (ammeter)  during  the   discussions as above. For more details, exact test
           changeover.                                       values and test procedure refer to IEC 60044-2.
   512   513   514   515   516   517   518   519   520   521   522