Page 862 - Industrial Power Engineering and Applications Handbook
P. 862

25/81 6 Industrial Power Engineering and Applications Handbook

                    Parallel
                   group = N2                                                        R,
                                                           Series                       Series
                                                           reactor                     reactor
                                                                                 JRl+n
                                                   1111                          1111
                                                   1111                          1111








         (a) Single  star  seriesiparallel capacitor   (b) Double star series/parallel capacitor banks with line side series reactors
            banks with neutral side series reactors
                                                  Figure 25.5


         voltage.  Small voltage adjustments by the manufacturer may   with external fuses and a fault would mean the fallout of
         also be essential when series  reactors are being used.   all  units. A  unit  with  internal fuses, however,  may  not
                                            192         pose such an eventuality,  as the fault would result in the
         No. of  single phase units required per phase  = - 64
                                                =
                                             3          failure of just one or two elements of that unit and may
         We may therefore consider a double star system, each having   not  cause  an  overvoltage.  Similarly,  metallized,  self-
         a  configuration  for  each  phase of  4 x  8  units,  that  is, four   healing type capacitor units may have fewer problems of
         units in series group to make up the required phase voltage   this nature, as discussed in Section 25.3. We give below
         and  eight  in parallel  group to  make up the  required kVAr
         (Figure 25.6).                                 the formulae provided by leading capacitor manufacturers
                                                        to calculate the magnitude of overvoltage in the event of
                                                        a failure of one or more units in a group of series/parallel
                                                        combination of capacitor units. It will help in rearranging
         25.5.1  Precautions against overvoltages on the   and balancing the capacitor units to contain the overvoltage
               failure of some units                    within  10%. To achieve this, there must be a minimum
         For large capacitor banks using a number of small identical   number of capacitor units  in parallel:
         units  per  phase the configuration  of  the  units  must  be
         such that a fault or a failure in one unit of a phase should   (i)  Single-phase  units  connected  in  parallel  The
         not result in an overvoltage of more than  10% across the   voltage rise across the healthy units on the failure of
         remaining healthy units  in that phase. This requirement   a  unit  of  the  many  connected  in  parallel  can  be
         becomes more specific when the capacitor units are used   expressed by;
















                       -7
                       IIIIIIII








                           Figure 25.6  Configuration of a double-star capacitor bank making 14 400 kVAr
   857   858   859   860   861   862   863   864   865   866   867