Page 879 - Industrial Power Engineering and Applications Handbook
P. 879

Protection, maintenance and testing of capacitor units  261831
                  Safe zone   Zone-1  Zone-2   Hazardous zone   Minimum rating of fuses = 200% of  lc
                       --I----
            50                                         i.e. 2 x  6.82 A or 13.64 A
                                                         Select  from the  manufacturer's catalogue  16 A  fuses for
                                                       each  unit,  according  to  the  characteristics  in  Figure  26.2
            20                                         reproduced in Figure 26.3. The fuse characteristics  fall well
                                                       within the safe zone and provide adequate protection to the
                                                       units.  If  series  reactors  are  provided to  control  the  inrush
            10
                                                       current,  a  fuse  corresponding  to  150% of  lc, i.e.  of  10 A,
                                                       would be better to protect the unit more closely. We can see
                                                       from  Figure  26.2  that  in  an  internally  protected  unit  the
                                                       characteristics of the internal fuses will fall well below that of
                                                       an external fuse and provide a more exacting protection on a
                                                       mild fault.
          4 t::                                        7 Voltage transients


                                                       These may be caused by  internal  switchings or external
          0
          2                                            lightning strikes. HT capacitor units,  particularly.  may
          z                                            be protected through surge arresters against such voltage
          K                                            transients (Chapter 18). The voltage  rating of the surge
                                                       arrester may be chosen on the following basis:
                                                         For ungrounded systemi = V,
           01
                                                         For grounded systems = 0.8 V,
                                                       See also Table  18.2
                                                       8 Voltage unbalance
                                                       An unbalance in the supply sy\tem causes an okervoltage
          0 013
          0 01
                                                        20 000
                                           3000  1  10000
                          100 200  300  5001000
              10    30  *Fault current (Amp ) rms -    10000
                                                        4 hrs
                                             5000
         @ - Characteristic of a 10A external fuse from Figure 26 3
         0- Characteristic of a 16A external fuse from Figure 26 3
         0- Probability curves for case  rapture
         ' Use asymmetrical rms values for transient faults   1000
         Figure 26.2  NEMA probability curves for a case rupture and
         selection of  internal and external fuses
                                                        ~100
                                                        4
         rupture  is not  eliminated. An  unbalance protection is a   0
         better choice in such cases, which may isolate the faulty   E
         unit  much  faster than the luses. When it is so, the units   E  10
         remain intact. At this stage visual checks can be made to   c
                                                        2
         find all such units that  may be excessively hot or have   t!
         bulged  out.  The  capacitance  of  the  units  can  also  be   ?
         measured  to identify the faulty  unit(s)  or the extent of   10
         damage to individual units and take corrective steps before
         reahitching the units. Example 26.1 illustrates a simple
         procedure  to select external  HRC fuses. The  fuses are
         provided separately for each unit.               01

         Example 26.1
         Consider the same units as those in Example 25.2 where
          V,,  of  each unit = 11 kV                     0 01   RMS symmetrical prospective current (Amp ) -
                  kVAr = 75                                 10          10         100         lo00
                    N1 = 4
                    N2  = 8
                     I,  = 6.82  A                     Figure 26.3  Timehrrent characteristics for  11 kV  HRC
                  and If = 65.47 A                     fuses (Courtesy: GEC Alsthom)
   874   875   876   877   878   879   880   881   882   883   884