Page 881 - Industrial Power Engineering and Applications Handbook
P. 881

Protection, maintenance and testing of capacitor units  261833
         and for an ungrounded system                   time delay of a few seconds can be  introduced into the
         Vu = 3 x 511.6  J  1535 V                      trip circuit. Sensitivity and the setting of  the relay will
                                                        depend upon the size of the banks and the sensitivity of
         If  the ratio of  VT  is 44 kVillO V, then the voltage across the   the  system, i.e,  whether  an  alarm  or  indicator  will  be
         open delta                                     sufficient initially while  repairs  are  undertaken  during
          ~  1535 x  110                                off-peak periods, or whether a trip will  be needed. The
             44000                                      amount  of  unbalance current can be  determined by  the
         =384V                                          following formula:
         and suitable NDR may be selected for this voltage                                    (26.2)
           For more than one capacitor bank one RVT for each bank
         will  be  necessary for  the  correct  discharge  of  each  bank,
         (Figure 26 5)  An  RVT,  if  provided with  an  additional star-   (established by the capacitor manufacturers)
         connected tertiary winding  rated for  110 V  line  to  line, can   where I,  = imbalance current through the interconnected
         also check the discharge condition and its duration and  if  it   neutral, and
         meets the design requirements  This can even be monitored   I,  = current per capacitor unit.
         remotely through a relay and control panel
                                                        Note
         Note                                           Current-sensing  protection  i\  found  to  be  more  accurate  than  a
         When an  RVT  is  being  used  for the  purpose  of  discharge,   voltage  sensing.  It  ia  therefore  recommended  that  the  unit\  are
         also no protective fuses are recommended to ensure a positive   arranged  in double  $tar as far as possible.
         discharge. On a trip, the RVT is programmed to be connected
         automatically to the capacitor units to discharge them.
                                                        (iii) Ampere meter mrthod
                                                        To  monitor the health  of a capacitor  uiiit  il is advisable
         (iij Ciirt.etit iit~brrltrric~ nirthorl        to provide an ammeter in each phase. When it i\  found,
         Thi\  method  is  applicable  to  double-star-connected   that there is an unbalance not caused by voltage unbalance
         capacitor banks (Figure 26.6). In this method the neutrals   then  further investigations may  be conducted to replace
         of  the  two  identical  star-connected  banks  are  inter-   the defective unit(s) before a major  fad^ occurs.
         connected and a protection Neutral CT (NCT) is inserted
         through  it.  In a balanced state, there will  be  no current
         through  the  neutral. On  a partial or a  total  failure of  a   Example 26.3
         unit in either of the banks it will disturb the balance and   Considering the earlier Example 25.2 with 14 400 kVAr banks,
         taus  ;I  current  through  the  interconnected  neutral.  A   connected in  double star where
         ground  fault  relay  will  be  most  suitable  for  such  a   N, = 4
         requirement. To  avoid momentary transient trippings. a   N2  = 8



                                        T                              T           R






















                                                                       Bank-ll
                                      Bank-I  w L-
                                                        ~   ~
                                        1          Unbalance relay      1
                                               Star connected capacitor banks
               Figure 26.6  Detecting an unbalance in  double-star identical capacitor banks through a current unbalance method
   876   877   878   879   880   881   882   883   884   885   886