Page 887 - Industrial Power Engineering and Applications Handbook
P. 887

26/838 Industrial Power Engineering and Applications  Handbook
          ventilation  facilities should also be provided, either   Avoid any spillovers, leakage or vaporization of liquid
          louvres,  exhaust fans  or by  providing  an expanded   or disposal of a waste unit. One can use Araldite, solder
          metal enclosure, for the capacitors to ensure a free air   or any  other means to  stop a leakage.  If  this  is  not
          circulation around each capacitor unit (Figure 23.32).   possible,  collect carefully  all the chemical PCB and
          Concentration  of  capacitor banks  at  one point  in  a   carefully dispose it of.
          system may cause amplification of  harmonics, self-   Soaked rags, cloth or papers, must be destroyed in an
          excitation of machines, overvoltages due to switching   incineration  plant  at  1000°C. Disposal  at  a  landfill
          and unsatisfactory  working of audiofrequency remote-   area is not advisable for during rain they may be carried
          control apparatus. To overcome this, a concentration   by  storm drains into rivers,  canals or ponds.
          of capacitor banks at one point must be avoided as far   Old  units  should  not  be  sold  to  a  scrap  dealer  for
          as possible. These may be installed at different locations   similar reasons.
          in the system.
          A loose contact within the circuit, producing sparks,
          will generate high-frequency oscillations (harmonics).   26.3  Test requirements
          However small these oscillations are, they may raise
          the  system  voltage  and  frequency.  High-frequency   Below we discuss briefly recommended tests on a finished
          oscillations  will  also  reduce  the  impedance  of  the   capacitor unit  based on various IEC recommendations.
          capacitors xch a llfh and cause high currents, leading   For standards refer to the list provided at the end of the
          to premature failure of the capacitors. Loose contacts   chapter.
          must  therefore  be  thoroughly  checked.  It  is
          recommended that a capacitor circuit particularly be   26.3.1  Routine tests
          checked  periodically  for  loose  connections  or
          sparkings.                                  Routine tests are carried out on each capacitor unit.
          When the reactive control is not automatic, then during
          offpeak periods (such as during the night) it is important   (I) Capacitance measurement
          that some of the banks are dropped manually to avoid
          an overcompensation  and a consequent overvoltage.   This is to be determined at rated voltage and frequency
          It is advisable to periodically check the condition (i.e.   and can be carried out between 0.9 to 1.1 times the rated
          the  capacitance  value  C) of  each  capacitor unit  to   voltage  and  0.8  to  1.2  times  the  rated  frequency.
          detect failure of one or more of them and the consequent   Permissible tolerances in capacitance from the declared
          overvoltage  across  the  healthy  units.  This  can  be   values can be as follows:
          measured by any of the methods discussed in Section
          26.3.1(1). The capacitance  value  of  each  unit  must   For LT capacitor units up to 1000 V  For both self-
          fall within the permissible limits as indicated in that   healing and non-self-healing types:
          section.  The  failed  units,  if  any,  must  be  replaced   S%  to + 10% for units and banks up to  100 kVAr
          promptly  with units of the same rating and brand to   5% to + 5% for units and banks above  100 kVAr.
          avoid any performance variation. If this is not possible   For HT capacitors
          then the banks must be balanced  by  readjusting the   5% to + 15% for capacitor units or banks containing
          units. When the banks are connected through a series   one unit per phase
          reactor, the value of the reactor must also be readjusted   5% to + 10% for capacitor banks less than  3 MVAr
          to match changed parameters. Otherwise the reactor   0% to + IO%  for capacitor banks from 3 MVAr to 30
          may resonate with the fifth or the seventh harmonic,   MVAr
          for which it is designed, and cause an overvoltage.   0% to + 5% for capacitor banks above 30 MVAr.
                                                      0  For series capacitors
        26.2.1  Precautions in handling a capacitor unit   These are usually HT capacitor units/banks:
              with PCB                                  f7.5% for capacitor units or banks containing one unit
                                                        per phase
        Although the manufacture of PCB-filled capacitor units   * 5% for capacitor banks less than 30 MVAr
        has been discontinued, for older installations some may   k3% for capacitor banks 30 MVAr and above.
        still be used. For the benefit of their users we give below
        the precautions that they must take when handling these   Methods to determine the capacitance of a
        units:                                        capacitor unit
                                                      Two common methods to determine this are:
         Do not inhale the vapour of this chemical.
         Avoid  its contact with eyes and skin.       0  Voltage method and
         Avoid its contact with birds and animals.    0  Bridge method.
         Avoid its contact with animal feed.
         Do not re-use contaminated paper and cloth.   In the voltage method the normal voltage is applied across
         In the event of contact with the human body, wash the   the capacitor terminals and line current, I,, is measured.
         skin with soap and water and the eyes with clean running   The value of capacitance, C, can be determined from the
         water.                                       equations provided in Section 23.5.2. In the bridge method
   882   883   884   885   886   887   888   889   890   891   892