Page 899 - Industrial Power Engineering and Applications Handbook
P. 899

27/850  Industrial Power Engineering and Applications  Handbook
                           \                             Limit the  switching  surges  as discussed in  Section
                            \
                            \                            23.5.1.  But  they  may  affect  the  steady-state  power
                                                         transfer  capability  of  the  system  (V,2/Z). Refer  to
                                                         reactive power control (equation (24.10)).
                                                         Adjust the steady-state voltage control by supplying
                                                         reactive  power  and  compensating  the  capacitive
                                                         content.
                                                         Suppress the harmonic contents.
                                                          Their ratings can be calculated by
        Figure 27.7  Six- or nine-limb zig-zag arrangement of
        windings to limit the harmonics                          V2
                                                             R=-
                                                                 W
                                                                 V2
        separators  in  between  to  reduce  the  iron  content  and   XL  =
        hence the induced magnetic field. The 1-4 characteristic
        can thus be varied as required by altering the gap, i.e. the   VAr = I*  . XL(neglecting R)
        iron  content  in  the  core.  They  are  suitable as  current   where
        limiters, and can also limit the occurrence of overvoltages.   R = reactor resistance - Wphase
        Where required, they can be provided with a tap-changing   X, = reactor reactance - Wphase
        facility to regulate their reactances. Likely applications   V = rated voltage of reactor - volts
        are:                                             W = reactor loss - wattdphase
                                                       VAr = rated output - VAr/phase
          Voltage  stabilization  and control  of  temporary  over-   I  = rated  current of reactor - A
          voltages.
          Flicker  control  in  industrial  supplies  through  V  =   27.4.2  Current limiting or series reactors
          L (dildt) (Section 6.9.4).
                                                       These are connected in series in  a circuit, as shown in
                                                       Figure 27.9 and are meant to limit the high inrush current,
         27.4  Application                             such as during switching of HT capacitor banks (Section
                                                       23.10). They may also be used to limit the currents under
         Some of the applications where a power reactor can be   fault conditions  by  adding to the circuit  impedance  to
         used  to provide a  reactive  support or compensation to   match with the breaking capacity of the interrupting device
         improve the quality of a power system are noted below.   when the fault level of the system may exceed this. Some
                                                       reactor connections are illustrated in Figure 27. IO. They
                                                       are  also  used  for load  sharing  of  two power  systems.
         27.4.1  Shunt reactors or compensating reactors
                                                       They are connected in the circuit permanently and may
         These are meant for parallel connections  to absorb the   have  a fixed  or  variable reactance,  rated  continuously
         reactive power (capacitive current) of the system and are   and can be made to have linear (fixed reactance) or non-
         generally  used  on  transmission  and  large  distribution   linear magnetic  characteristics  as required. When  they
         networks,  as  shown  in  Figure  27.8. They  may  have  a   are required to limit the inrush currents, fixed reactance,
         fixed or variable reactance, rated continuously, and any   linear  reactors  should  be  preferred.  During  a  fault
         of  the magnetic characteristics  as  illustrated  in Figure   condition, the reactance of the reactor should not diminish
         27.2. Broadly speaking, they can perform the following   due to the saturation effect. This is an essential requirement
         functions:                                    to  limit  the  short-time  fault  currents.  Ideally,  current







          AJ-  I  I                   V   I






            Lumped or leakage capacitance
                                                        Figure 27.9  Use of current limiting reactor, (1) to limit the
         Figure 27.8  Use of a shunt  reactor to compensate for the   fault current, or (2) to limit inrush current during a capacitor
         reactive power                                switching
   894   895   896   897   898   899   900   901   902   903   904