Page 900 - Industrial Power Engineering and Applications Handbook
P. 900

Power reactors  271851






                                                                                              c




                                                                                             T












          (a) Feeder connections   (b) Tee-off connections         (c) Busbar sectionalizer connections
                                         Figure 27.10  Reactor connections


        limiting reactors must have no-iron circuit (air core or   adequate impedance on fault. They may also be employed
        coreless  type). The  iron  core  type  provide  non-linear   as  a  current  limiter,  such  as  shown  in  Figure  27.9.  It
        saturating type characteristics, and at overcurrents have   must, however, be ensured that the voltage available across
        a tendency to diminish their reactance due to the saturation   the load does not  fall below  the permissible  level  as a
        effect,  while  the  reactors  are  required  to  offer  high   result of the voltage drop across the reactors. The reactors
        impedances to limit the fault currents. The coreless type   for such applications should be continuously rated.
        will provide a near-constant reactance at all currents due   For Figure 27.9 the rating of the series reactor can be
        to the absence of an iron core and hence, their preference   determined by
        over other types for such applications.
          Similarly, gapped iron core reactors as shown in Figure   VAr   '  V,  I
        27.4, in which the iron core content is reduced by providing
                                                                    "'
        an  air gap or non-magnetic  material  between  the core   x, = - Rlphase
        laminations,  also  raise  the  saturation  level  (the  core   43.1
        remaining unsaturated, Figure 27.1 1) to help provide an   where
                                                         VAr  = rating of the series reactor (Volt. Amp)
                                                           V, = rated voltage drop of the reactor phase to phase
                                                               in volts
                        I                I                   = voltage induced in the reactor when operating
                                                               at rated  current and rated reactance
                                                            I  = rated current of the reactor (A)
                                                           R  = resistance of  the reactor
                                                       ..  R << XI- (less than  2-372  of XL) may  be ignored

                                                       Example 27.1
                                                       Consider  a  three-phase  reactor  having  the  following
                                                       specifications:
                                                        V, = 33 kV
                                                        V, = 3% of  the system voltage  (phase to phase)
                                                       System current,  I, = 650 A
                0       1        2       3       4
                          Peak current in the  --t     To  determine the size of the reactor
                            faulty region
                                                       V. in absolute  terms
                                                          3
         Figure 27.11  Typical characteristics of a current  limiting   =-x33
         reactor (coreless, gapped iron core or magnetically shielded   100
         core type)                                    = 0.99  kV, say  1 kV
   895   896   897   898   899   900   901   902   903   904   905