Page 902 - Industrial Power Engineering and Applications Handbook
P. 902

Power reactors 27/853
                         Grid bus
                         I
                                       I
                                           Generator
               Transformer            1 kVA, 11 kV
                                         2500
             5000 kVA, 33/11 kV            4, = 25%
               Z,, = 7.1 5%   8  T         (Reactive)
                (Reactive)
                                                           Z,, = 7.15%           z,,  = 50%
                                                            (Reactive)           (Reactive)


                                                             Series
                                                            reactor x%
                                                                    f

                           3-phase loads                                              Fault
                             (a) Location of fault                     (b) Equivalent circuit

                                    Figure 27.13  Application of a series reactor


      where qq = equivalent p.u. impedance of the combined power   If the fault level is required to be limited to 50 MVA, a series
              system at the point of fault.          reactor  of  reactance,  XY0  may  be  introduced  into  the
      Consider the base level as 5000 kVA, 11 kV     transformer circuit, as illustrated in Figure 27.13(b),
      :.  Generator reactance at the new base        The new              -  5000
                                                                        eq  - 50 x 1000
             5000
        ~25~- (equation (13.1))                                           = 0.1  p.u.
             2500
                                                                        1
        = 50%                                        and the new reactance - =      +-  1
              1=-                                                      0.1   0.0715 + X   0.5
                            1
      and                 +-                                                (0.0715 + X) (0.5)
               Z,,  0.0715   0.5                     or                0.1 =
                                                                              0.571  5 + X
      or       Zes = 0.0625                                             X = 0.0535 p.u. or 5.35 YO
                                                     or
      :.   Fault level  = -          (equation (13.6))                  at 5000 kVA base and 11 kV
                    5000
                   0.0625
                                                     :.  A series reactor of  reactance 5.35% may be used to limit
                  = 80 MVA                           the fault to the required level.
                                            Relevant Standards
      ZEC           Title                                            zs          BS

      60289/1988    Reactors                                         5553 (1 to 8)   BS EN 60289/1995
                                  Relevant US Standards ANSVNEMA and IEEE
      IEEE 62/1995   Guide for field testing of electric power apparatus insulation. Part I - oil filled reactors

      Notes
      1  In the tables of Relevant Standards in this book while the latest editions of the Standards are provided, it is possible that revised editions
        have become available. With the advances of technology andor its application, the updating of Standards is a continuous process by
        different Standards organizations. It  is therefore advisable that  for more authentic references, readers should consult the relevant
        organizations for the latest version of a standard.
      2  Some of the BS or IS standards mentioned against IEC may not be identical.
      3  The year noted against each standard may also refer to the year of its last amendment and not necessarily the year of publication.