Page 914 - Industrial Power Engineering and Applications Handbook
P. 914

Carrying power through metal-enclosed bus systems 28/865
         The sir.e of the conductor therefore should be such that   The  standard  size  of  aluminium  flat  nearest  to  this  is
         its temperature rise  during a fault will  maintain its end   50.8 mm x  12.7 mm or (2" x 1/2'')  or any other equivalent flat
         temperature  below  the  level  where  the  metal  of  the   size (Tables 30.4 or 30.5).
         conductor will start to soften. Aluminium. the most widely
         used metal for power cables. overhead transmission and   This formula is  also drawn  in  the  form of  curves as
         distribution lines or the LT and HT switchgear assembly   shown  in  Figure  28.5,  l,c/A x  yit. (I,'  in kA)  versus
         and bu$ duct applications. starts softening at a temperature   final  temperature.  From  these  curves  the  minimum
         of around  180-200°C.  A\ a rule of thumb, on a fault a   conductor size can be easily found for any fault level, for
         safe temperature rise of  100°C above the allowable end   both aluminium and copper conductors and for any desired
         temperature  of  85°C or 90°C  of  the  conductor during   end temperature. As in the above ca\e
         norinal  service.  i.e.  up  to  185-1 90°C  during  a  fault
         condition,  is  considered  safe  and taken  as the  basis  to
         determine the size of the conductor. The welded" portion,
         such  a\ at the flexible joints.  should also be  safe up to
         thi4  temperature. Tin  or  lead  solder starts  softening  at   or   vG =  I   IO4
                                                            A
         around this temperature and should not be used for this   -   4 1.166 x  1.34255 x  IO"
         purpose.  It  is  ad\isable  to  use  brass  soldering  where
         high-injection pressing is not possible. Welding of edges   = 0.0799 (/\c  is in kAj
         is essential to sen1 off  flexible ends.
           T'o  determine  the  minimum  size of  conductor  for a   GeneraliLing,
         required fault level. I,,, to account l'or the thermal effects   I,,
                                                           x
         on11 one can use the following forinula to determine the   - ?G = 0.0799 for an operating temperature
                                                        A
         iiiiniinuin  size of' conductor for any fault lewl:     at 85°C and temperature at  1XS"C   (18.2)
                                                         Therefore. for the same parameters as in Example 28.2
                                               (28.1 )
                                                        A=-      x & ---  6253 nim'
         u here                                             0.0799
           0, = temperature rise  (in "C)              A small difference, if any. between this and that calculated
          I,,  = syminetrical fault current r.m.s. (in Amps)   above  may  be  due to  approximation  and  interpolation
           '4  = cross-sectional area of the conductor (in mm')   only.
         0c2,, = temperature coefficient of resistance at 20"C/"C,   This minimum conductor six will take account of the
              which  as  in  Table  30.1  is  0.00403  for  pure   heating effects only during the fault. irrespective of the
              aluminium and 0.00363 for aluminium alloys and   current rating of the conductor. The required  conductor
              0.00793 for pure copper                  size may be more than this. depending upon the continuous
           H  = operating temperature of the conductor at which   current it has to carry, as discussed latcr.
              the  fault occurs (in "C)
           K  = I. 166 for aluminium  and 0.52 for copper   Example 28.3
           /  = duration of fault (in seconds)         If  the  conductor  is  of  copper  then,  assuming  the  same
                                                       parameters,
         Example 28.2
         Determine the minimum  conductor size for  a fault  level  of   100 = 0.52 X (F 1'  x (1 + 0 00393 x  85) Y  1
         50 kA for one second for an aluminium conductor.       100
           Assuming the temperature rise to be 100°C and the initial
         temperature of  the conductor at the instant of  the fault 85°C
         then
              100 = 'E   [?I*     x (1 + 0.00403 x  85) x  1   = 416 mm2
                       x
                    100
                                                       Copper is one two thirds the  size of  aluminium for the
                                                       same parameters and the melting point of copper at almost
                                                        1083°C (Table 30.1) is approximately  I .S  times that  of
                                                       aluminium at 660°C. These melting points are also located
         or    A=- 50000 x  t'i1.166x1.34255           on the nomograms in  Figure 28.6. Refer to nomograms
                    100                                (a) and (bj for aluminium and (c) for copper conductors.
                 ~  625 6 mm2 for pure aluminium       The  same area  can  also  be  obtained  from  the  copper
                                                       curves of Figure 28.5. Assuming the sane end temperature
         or      = 617 6 mm2 for alloys of  aluminium   at  185°C. then  corresponding  to the operating curve of
                (assuming a2,, = 0 00363)              85°C.
                                                        I,,  -
                                                        - dt = 0.12                           (28.3)
         '.Welding of flexible ,joints \hould preferably  be  carried out  with   A
         liigh-in,jection pressinf  (weldin? hy prem heating). eliminating the
         IIW  01  urlding rod\.                        and for the same parameters as in  Example 28.3.
   909   910   911   912   913   914   915   916   917   918   919