Footings, Foundation Walls, Basements, and Slabs
One and Two-Fam-
Use of this table for sizing concrete and masonry foundation walls in Seismic Zones 3 and 4 shall be limited to the follow-
Walls shall not support more than 4 feet of unbalanced backfill.
Walls shall not exceed 8 feet in height. Mortar shall be Type M or S and masonry shall be laid in running bond. Ungrouted hollow masonry units are permitted except where otherwise indicated. Soil classes are in accordance with Unified Soil Classification System (Figure 6-13). Unbalanced backfill height is the difference in height of the exterior and interior finish ground levels. Where an interio
ing conditions:
1. a. b. 2. 3. 4. 5. 6. 7. 8. ily Dwelling Code,, Falls Church, VA).