Page 331 - Masonry and Concrete
P. 331

Masonry Garden Walls

             330   CHAPTER NINE




                                Recommended Spacing          Vertical Spacing of Joint Reinforcing
                                of Control Joints           None    24 inch   16 inch  8 inch
                                                                       1
                                Expressed as ratio of panel   2       2 ⁄2      3         4
                                length to panel height, L/H
                                With panel length (L) not     40       45       50       60
                                to exceed, feet

                               FIGURE 9-19

                              CMU control joint spacing. (from NCMA, TEK 10-1, National Concrete Masonry Associa-
                              tion, Herndon, VA).



                                 The height of freestanding CMU garden walls is limited by the same
                              height-to-thickness (h/t) ratio as brick walls. Maximum wall height
                              should not exceed 18 times the wall thickness. An 8-in. wall can be a
                              maximum of 12 ft. high. Lateral support must be provided at the same
                              ratio of 18 times the thickness of the wall (Figure 9-3). This means that
                              an 8-in.-thick wall would require pilaster stiffening every 12 ft. With
                              hollow CMU walls, vertical reinforcing steel can be grouted into the
                              cores of the units, which essentially creates an integral pilasters where
                              the wall thickness remains the same (Figure 9-21c). Alternatively, pro-
                              jecting pilasters may be created with standard units bonded into the
                              wall (Figure 9-21b) or with special pilaster units (Figure 9-21a). Pro-
                              jecting pilasters may be hollow, grouted, or grouted and reinforced,
                              depending on the lateral loads and the height of the wall. In seismic
                              areas and coastal areas subject to hurricane winds, grout and reinforc-
                              ing steel will be required to meet code requirements for load resistance.
                              Ungrouted hollow pilasters should project from the wall a distance
                                                     1
                              equal to approximately   12 of the wall height, and their width should
                                                       1
                              be equal to approximately   10 of the horizontal span between supports.
                              Using either standard or special units based on the 8 16 module will
                              produce an 8-in. projection with a 16-in. width, which is adequate for
                              wall heights of up to 8 ft. and pilaster spacings of up to 12 ft.
                                 The course of block just below the coping in a CMU wall should be
                              filled solidly with grout. Lay pieces of screen wire in the bed joint
                              below this course so the grout will not flow down into the rest of the
                              wall. Cap the wall with flat coping block or stone and install flashing
                              in the same way as for brick walls (Figure 9-22).


                   Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                              Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                               Any use is subject to the Terms of Use as given at the website.
   326   327   328   329   330   331   332   333   334   335   336