Example of a Steel Frame Building Retrofitted Chapter  5 341



               TABLE 5.24 Designed Concentric Braces

               Brace Name                    Story Number          Profile
               Main building (X-direction)   1                     2UNP80
                                             Floor                 2UNP100
               Main building (Y-direction)   1                     2UNP80
                                             Floor                 2UNP140
               Sports building               Floor                 2UNP80





             show that due to high forces acting in the beams, plate girders should be used as
             link beams. This adds to the costs and complexity of the retrofit method.
                Similar to the building retrofitted with concentric braces, the columns of the
             building adjacent to the braces need to be retrofitted; however, other columns of
             the building are not vulnerable because they have no contribution in lateral
             load-bearing. Location of the added eccentric braces is shown in Fig. 5.29.
             The designed profiles of the concentric braces are presented in Table 5.26.
             As can be seen, larger profiles are needed for the eccentric braces compared
             with the corresponding concentric braces. The designed section of the link
             beams are presented in Table 5.27. The length of the link beams in all the bays
             is assumed to be 60cm. As an example, the results of the evaluation of the build-
             ings in terms of DCR of the structural members in the retrofitted model by
             eccentric braces are shown in Fig. 5.30.
                As stated, because the existing beams in the buildings cannot resist the
             forces from the eccentric braces, new beams have to be added beneath the exist-
             ing beams (see Fig. 5.20). At each bay, the significant shear forces in the dis-
             tance between the existing and the added beams which represents the short
             column behavior should be checked. Based on the Iranian National Building
             Code; Part 10: Steel Building [6], the compressive sections experiencing con-
             siderable shear forces have shear strengths determined based on Eq. (5.35),if

                                   3185
             the section satisfies  h    p .
                                     ffiffiffiffi
                               t w
                                     F y
                                        F v ¼ 0:4F y                   (5.35)
                The demand shear force and the shear capacity of the column section are 6.9
             and 30.2ton, respectively; hence, the short columns between the existing and
             added beams are not vulnerable in shear.
                The short columns should also be checked for web local yielding. Based on
             the Iranian National Building Code; Part 10: Steel Building [6], when the