Page 129 - Applied Photovoltaics
P. 129

Standards Australia (2005) also recommends that plugs, sockets and couplers should
                     be multipolar and rated for DC voltage at least 1.2 times the array open circuit
                     voltage. Their current rating should equal or exceed that of the associated cables.
                     Plugs and socket outlets normally used for AC mains power should not be used. Refer
                     to Standards Australia (2005) for details and further recommendations.

                     6.8.5 Earthing (grounding)
                     Earthing involves the provision of low resistance paths from selected points within
                     the PV system to earth (ground). Standards Australia (2005) provides a decision
                     flowchart to help determine the necessary equipment earthing. Earthing is not
                     required in some cases, including if double insulation is used. Equipment grounding
                     involves ensuring all metal enclosures and parts of the array frame that might be
                     touched by hands are well earthed.

                     System earthing (Ibid.) normally involves connecting one of the current-carrying
                     conductors (commonly the negative but possibly the positive or a centre tap) to earth.
                     The manufacturer’s requirements for power conditioning equipment, such as
                     inverters, should be taken into account in choosing the most suitable arrangement of
                     system earthing. This aspect is considered in detail by Standards Australia (2005).

                     Good contact with the earth is required via a ground rod. Contact with subterranean
                     water helps. Rocky soil may be a problem.

                     6.8.6 Lightning protection
                     Lightning protection is required when a system is deemed to be prone to lighting
                     (Standards Australia, 1999–2000a) but is usually not necessary (Standards Australia,
                     2002). Such protection may include clamping circuits, metal oxide varistors, transient
                     absorption zener diodes and/or circuit breakers. These act as open circuit devices until
                     the voltage across them rises above the rated threshold breakdown voltage, at which
                     point they provide a short-circuit to ground (see Florida Solar Energy Centre, 1987).
                     They will not protect against a direct lightning strike. The system design guidelines
                     (Standards Australia, 2002) include an informative appendix on lightning risk
                     assessment and protection, and common practices are described by the IEA-PVPS
                     (2003).

                     6.8.7 Metering and alarms

                     Battery terminal voltage, input current and, in the case of a system including a backup
                     generator, generator run hours, should be metered. Alarm indicators of high and low
                     battery voltage are desirable (Standards Australia, 2002).

                     6.8.8  Battery housing and signage

                     Batteries must be protected from the elements, whereas people, the natural
                     environment and equipment must be protected from acid and the risk of explosion of
                     evolved gas. Batteries can be buried below the frost line in water-tight enclosures,
                     with drain holes, if sub-zero temperatures are anticipated, or housed in a building
                     where temperatures remain above zero. The batteries themselves should never be
                     placed directly onto concrete, as this will increase the self-discharge rate, particularly





                     116
   124   125   126   127   128   129   130   131   132   133   134