Page 272 - Boiler_Operators_Handbook,_Second_Edition
P. 272

Water Treatment                                                                                     257


               gree and type of chemical treatment. See the discussion  It’s like having a boiler inspector, always better to have
               on water as a consumable.                            some other, somewhat disinterested, party looking at
                                                                    the chemistry. It’s really best if the consultant doesn’t get
                                                                    to sell you the chemicals.
               CHEMICAL TREATMENT                                       A water treatment program only has two goals,
                                                                    prevent corrosion and prevent scale formation, it’s that
                    If there’s any time for you to make a bad decision  simple. The causes of corrosion and scale formation
               regarding reading this book it’s right here. I know that  have to be understood to prevent them and knowing
               many times chemical treatment of water is treated like  how the chemicals prevent (or enhance) those condi-
               a black art but hopefully you have had no trouble un-  tions must be understood to maintain proper chemical
               derstanding any other part of this book and this section  water treatment. The process of obtaining representative
               should be no exception.                              water samples and properly testing them for chemical
                    I will admit that chemical treatment suppliers  content has been covered and how to use that informa-
               have, and will continue to, make it difficult to under-  tion to achieve the goals of the program is described in
               stand  what  their  product  is  doing  by  using  obscure  the paragraphs that follow.
               names and numbers to label what are really common        Recording everything that happens, every test run
               chemicals. The first rule in understanding your chemi-  and follow-up actions is important to understanding
               cal treatment program is knowing what’s in the con-  what’s happening and the result of your actions. Don’t
               tainer. There aren’t that many compounds for water  limit the record to the space provided on the log sup-
               treatment and they do the same thing regardless of the  plied by the chemical treatment supplier. I’ve already
               name or number on the barrel so you can understand  mentioned a few incidents that can occur and alter water
               the purpose and function of the chemical if you know  chemistry but there are many others and I’m counting
               what’s in it.                                        on you knowing enough about it to determine when
                    If your supplier will not tell you my suggestion  something has altered the chemistry and logging it in
               is to go find one that will. Given the true title of the ac-  addition to correcting for it.
               tive chemical and the following paragraphs you should     Your boiler or water system has boundaries and
               know enough to properly maintain chemical treatment  contains a certain volume of water. That volume or
               of your plant’s water.                               weight of water contents can be determined from manu-
                    I’ve said it before and I will repeat it; the only  facturer’s instruction manuals and estimates using
               person that can effectively operate a water treatment  actual measurements and the data in the pipe tables in
               program is the educated boiler operator. Those chemi-  the appendix to calculate the volume and determine
               cal treatment consultants that arrive at the plant every  the weights. Once you have an initial volume or weight
               month or two have no idea what has transpired between  determined you know what the weight of the water in
               visits. They can’t possibly know that the boiler was shut  the system or boiler will be when it’s cold, at 70°F where
               down, drained and refilled, left sitting idle or operated  water weighs 62.27 pounds per cubic foot. Freezing
               continuously. They might if they bothered to look at the  (32°F) water weighs 62.4.
               operator’s log but I don’t recall ever seeing one do that.     Once the system is up to operating temperature the
               They may not know that there was an upset in the level  weight will be lower and you may want to adjust your
               controls and the operator used the bottom blowoff to re-  data for the effect of thermal expansion. Determine the
               store water level several times dramatically reducing the  ratio of cold to operating by dividing the specific vol-
               chemical levels. All too often I’ve noticed that a water  ume of water at 70°F (0.016025) by the specific volume of
               treatment consultant has changed a program due to an  water at the operating temperature using the data from
               upset condition with resulting over-treatment.       the steam tables and multiplying it by the weight of the
                    You and your fellow operators are able to commu-  water when it’s cold. That’s the weight of the water in
               nicate so you’re aware of all the variables that affect the  the system when it’s operating. Move the decimal place
               chemical concentrations in your boiler water and can  of that result six places to the left or, if you’re using a
               make sound decisions about changes in the treatment  calculator then divide by one million, to know how
               program much better than a consultant. Knowing this, I  many million pounds of water are in your system. Un-
               trust you’ll be able to explain the activities that changed  less it’s a very big system the number will be small but
               the water content to your consultant so you get better  you will know how many million pounds of water you
               service. Note that I didn’t say get rid of that consultant.  have so the results of chemical tests in parts per million