30                                                                                Boiler Operator’s Handbook


               automatic  valves.  Of  course  I  should  say  that  applies  forming the owner that it was “just a puff” that occurred
               to service engineers that worked for me at Power and  as the burner started. Don’t ever let anyone convince
               Combustion. In some instances a service engineer will  you that a puff is anything other than an explosion. A
               leave  a  job  that  doesn’t  light  off  properly;  as  far  as  I  puff is simply an explosion that did no or limited dam-
               know we never did.                                   age. Every puff you experience should be considered a
                    I always tell this story because it introduces another  warning and is not be tolerated because sooner or later
               term in a manner that operators understand. One of the  whatever is causing the problem will get worse and you
               reasons Power and Combustion provided quality boiler  will experience an explosion that does some serious
               and burner installations was the interaction between the  damage.
               design engineer (me) and the technicians in the service     What causes explosions, including puffs? It is the
               department who performed the work in the field. They  direct result of an accumulation of a flammable mixture.
               never hesitated to show me how I had screwed up or call  Make no mistake about it, when you’re burning a fuel
               when they had a problem they couldn’t resolve. In the  you are creating an explosive mixture because there is
               1980’s my service manager at Power and Combustion  no difference between a mixture of fuel and air that will
               was a gentleman named Elmer Sells. Elmer and I got  burn and an explosive mixture. The reason we can safely
               along well because we’re both hillbillies, natives of the  fire a boiler is we burn the explosive mixture at the same
               Appalachians, I grew up in western New York State and  rate that we create it. It’s only when the mixture doesn’t
               he grew up in West Virginia. We were into the start-up  burn and accumulates that we have an explosion. We
               phase of a project to convert three oil fired boilers at Fort  control the combustion by controlling the rate of burn-
               Detrick to gas firing.                               ing. When an accumulation ignites it burns at a rate
                    I got a call from Elmer asking that I come out to  dictated by nature and that’s a lot faster than our normal
               the plant to look at a problem they had. When he called  fire, so fast that the products of combustion expanding
               he used that West Virginia drawl that normally meant  can create a pressure wave which will create a force of
               he figured he had me, so I knew I was in trouble before  18 to 70 psig. The explosions we experience and call a
               I even left. I arrived right after lunch time and found  puff were simply small accumulations of an explosive
               Elmer standing next to the largest boiler, a four burner  mixture which did not produce pressure high enough to
               unit rated at 140,000 pph. Working that WV drawl he in-  rupture the furnace.
               formed me they had just purged the boiler and he would     It’s not always possible to avoid a puff or rough
               like me to try to light off the bottom left burner.  light off. They occur when burner systems fail to repeat
                    As I climbed up the ladder to the burner access  the conditions established when they were set up. Mate-
               platform I noticed the observation port on the burner  rial can plug orifices, linkage can slip, regulator springs
               was open so I stood off to the side of the burner while I  can soften and many times a combination of minimal
               started it. The gas-electric ignitor started fine but there  factors  can  combine  to  prevent  a  smooth  light  off  or
               was a little delay after I opened the last main gas shut-  burner operation. If you experience a puff you should
               off valve. The burner ignited, the boiler shuddered, and  consider it a warning sign that something is going
               a tube of flame shot out of that observation port about  wrong and do something about it. If your sense of what
               six to nine feet long. I had my finger on the burner stop  has been happening with your burner is sound, you may
               button immediately but realized the burner was operat-  be able to correct the problem yourself but you should
               ing normally. Then I turned to look down at Elmer who  keep in mind that more than 34% of boiler explosions
               was standing there with his hands clasped behind his  are attributed to operator error or poor maintenance;
               back while rocking back and forth on his toes and heels.  make adjustments only when you are confident that you
               He dropped his broad smile and said, again with that  understand what is causing the delayed ignition. If you
               WV twang “little rough, ain’t it?” I agreed and realized  aren’t certain, it’s much wiser to call for a service techni-
               what I had done wrong so we set out to correct the prob-  cian that has experience with burner adjustments.
               lem. Today those burners light off quietly and smoothly.     I  think  it’s  important  that  a  flame  begin  within
               The lesson to be learned here is any roughness on light  the throat of the burner where heat radiating from the
               off is just another form of explosion and shouldn’t be  refractory throat provides ignition energy. I normally
               tolerated.                                           don’t  see  a  stable  flame  on  a  burner  without  a  good
                    In recent years I’ve encountered facilities where  refractory throat. A boiler just south of Baltimore had a
               the contractor that placed the equipment in operation  furnace explosion in 1993 that was due to the improper
               couldn’t establish a smooth light off and left the job in-  adjustment of the burner such that the UEL was estab-