48                                                                                Boiler Operator’s Handbook


               written log, however, may only include a record of data  Boiler outlet water temperature: Hot water heating
               by shift or on a four or two-hour interval. There is little   boilers are typically controlled to maintain this
               value to hourly data other than requiring the operator to   temperature. It is required for output calculations.
               be within the vicinity of each piece of equipment every
               hour. It’s a matter of professionalism, operators with a   Boiler water flow: Hot water boilers, especially certain
               sense of being a professional enter data in the log every   types of HTHW boilers, require a controlled flow
               hour to demonstrate that they’re watching the plant.     of water. The value is required for output calcula-
                                                                        tions and should also be monitored for reliability
               Suggested Matter and Data to Record                      because minimal flow should trip a limit switch.
                    Here is an abbreviated list of things that should
               be documented in the boiler plant log along with some   Booster pump pressure: See condensate pump pressure.
               good reasons for maintaining a record of the values or
               information. It’s arranged  in alphabetical order and   Burner gas pressure: The gas pressure at the burner is
               many of these items won’t apply to your plant so you     indicative of input and should be monitored for
               wouldn’t include them in your log.                       consistency relative to load. Increases in gas pres-
                                                                        sure relative to load are indicative of plugging of or
               Air heater outlet air temperature: Monitoring the heated   damage to the gas burner. Decreases are indicative
                    air temperature along with flue gas inlet and outlet   of failure or damage to the gas burner.
                    temperatures provide an indication of fouling of
                    the heat transfer surfaces, leakage past seals or   Burner oil pressure: The oil pressure at the burner is
                    through corroded tubes, and other performance       indicative of input and should be monitored for
                    problems with the air heater.                       consistency relative to load. Increases in oil pres-
                                                                        sure relative to load are indicative of plugging of
               Annual inspection: The operator’s narrative should re-   or damage to the burner gun or the atomizing me-
                    cord the annual (bi-annual or fifth year in certain   dium controls. Decreases are indicative of failure
                    jurisdictions and with certain types of pressure    or damage to the burner gun or atomizing medium
                    vessels) inspection of the boilers and pressure ves-  controls.
                    sels in the plant. Inspections are required by law
                                                                    City water temperature/pressure: See makeup water
                    in every state so documenting that it happened is
                    imperative. Don’t rely on the inspector, some of
                                                                    Combustibles: Monitoring the combustibles content of
                    whom have been known to lose paperwork. The
                                                                        the flue gas can lead to early detection of burner
                    record should include the name of the National
                                                                        problems and fuel air ratio control failure. Larger
                    Board  Certified  Inspector  and  any  findings  that
                                                                        plants may actually control air to fuel ratio using
                    inspector relates to the operator.
                                                                        combustibles and monitoring that value is very
                                                                        important to them.
               Blowdown heat exchanger drain temperature: This data
                    provides a means of calculating the cost of heat lost
                                                                    Combustion air temperature: Frequently this is also the
                    to blowdown. The temperature is an indicator of
                                                                        boiler room temperature. The combustion air tem-
                    the performance of the heat recovery system and
                                                                        perature is the base for a boiler heat loss efficiency
                    blowdown/makeup relationship. The drain also
                                                                        determination.
                    dumps to a sanitary sewer which, by Code and
                    law, can’t be higher than about 140°F so it’s also a  Contractor’s activities: The operator’s narrative should
                    record of compliance.                               describe which contractors were in the plant,
                                                                        when they were there, how many men, and what
               Boiler inlet water temperature: For steam boilers it is an
                                                                        they were working on. It wouldn’t hurt to list the
                    indication of heat lost in feedwater piping or heat
                                                                        names of each of the contractor’s employees. Less
                    added by feedwater heaters and economizers. For
                                                                        needs to be recorded if there’s a contractor’s log.
                    hot water boilers it is an indicator of load, required
                                                                        Even if there is, the operator’s log should note the
                    for output calculations. The inlet temperature for
                                                                        presence of the contractors as well, use a simpler
                    fluid heaters and vaporizers serves the same pur-
                                                                        record such as “XYZ Contractors on site at 8:20
                    poses.
                                                                        a.m.—seven men.”