Boiler Plant Calculations                                                                        211



                                                             Table 11-19

























































                HEAT LOSSES IN THE                                  City Water                     50F    18 Btu/lb
                CONDENSATE RETURN SYSTEM                            Hot condensate                 194 F  162 Btu/lb
                                                                    Water heating (50F to 194F)           144 Btu/lb
                     The purpose of this section is to illustrate   Fuel energy used to heat city
                how energy is lost in the condensate recovery sys-      water to 194 F with 80%
                tem serving a 100 psig steam system.                    efficient boiler                  180 Btu/lb


                Example 1. Assuming that condensate should re-      Water heating (194F-338F)             144 Btu/lb
                turn  to  the  receiver  at  194F,  what  losses  are  in-
                volved  for  each  pound  of  cold  make-up  water   Fuel energy used to bring water
                used to replace steam and condensate lost from          to saturation 338F with boiler    180 Btu/lb
                the system?
                                                                    Latent Heat of 100 psig steam         880 Btu/lb