112                    CHAPTER FOUR

             For square or rectangular footings subject to overturning about two principal
           axes and for unsymmetrical footings, the loading eccentricities  e and e are
                                                                 2
                                                           1
           determined about the two principal axes. For the case where the full bearing
           area of the footings is engaged, q is given in terms of the distances from the
                                    m
           principal axes, c and c , the radius of gyration of the footing area about the
                            2
                       1
           principal axes, r and r , and the area of the footing A as
                           2
                      1
                                 P      e 1 c 1  e 2 c 2
                             q m      1         2               (4.18)
                                 A       r 1 2  r 2
           For the case where only a portion of the footing is bearing, the maximum pres-
           sure may be approximated by trial and error.
             For all cases of sustained eccentric loading, the maximum (edge) pressures
           should not exceed the shear strength of the soil and also the factor of safety
           should be at least 1.5 (preferably 2.0) against overturning.
           AXIAL-LOAD CAPACITY OF SINGLE PILES


           Pile capacity Q may be taken as the sum of the shaft and toe resistances, Q
                      u                                            su
           and Q , respectively.
               bu
             The allowable load Q may then be determined from either Eq. (4.12) or (4.13):
                            a
                                      Q su   Q bu
                                 Q a                            (4.19)
                                         F
                                      Q su  Q bu
                                 Q a                            (4.20)
                                      F 1   F 2
           where F, F , and F are safety factors. Typically, F for permanent structures
                         2
                   1
           is between 2 and 3, but may be larger, depending on the perceived reliability
           of the analysis and construction as well as the consequences of failure.
           Equation (4.13) recognizes that the deformations required to fully mobilize
           Q and Q bu  are not compatible. For example, Q may be developed at dis-
                                               su
            su
           placements less than 0.25 in (6.35 mm), whereas  Q  bu  may be realized at
           a toe displacement equivalent to 5 to 10 percent of the pile diameter. Conse-
           quently, F may be taken as 1.5 and F as 3.0, if the equivalent single safety
                                        2
                   1
           factor equals F or larger. (If Q su /Q bu  1.0,  F less than 2.0 is usually considered
           as a major safety factor for permanent structures.)
           SHAFT SETTLEMENT
           Drilled-shaft settlements can be estimated by empirical correlations or by
           load-deformation compatibility analyses. Other methods used to estimate settle-
           ment of drilled shafts, singly or in groups, are identical to those used for piles.