Table 4.1  (continued)


 1   2   3   4  5  6   7   8   9   10   11   12   13   14
 Flammable   Formula   Melting  Boiling  Relative  Flash   Flammable limits   Ignition   Minimum  T  classof  Apparatus
 materials   point   point   vapour   point   temperature   igniting   suitable   group
 density                             ament   apparatus
     LFL   UFL   LFL   UFL

 "C   "C   "C   Vol.%   Vol.%  mg/L  mg/L   "C   mA
 kerosine   Mixture   -   150   -   38   0.7   5  -  -   210   -   T3   IIA
 (RS)-P-mentha-l,&   C10H16   -75   175   4.66   42   0.7   6.1   -   -   237   -  t  IIA
 diene
 (dipentene)
 metaldehyde   2469   ll2*   6.07   36   -   -  t  IIA
 methane (iiredamp)   -182   -161   0.55   -   595   85   T1   I
 (see 7.41)
 methane(indushial)                    -    T1     IIA
 (see clause 37)
 methanol   -98   65   1.11   11   6.7   36   73   350   455   70   T1   IIA
 2-methoxyethanol   -86   124   2.63   39   2.5   14   80   630   285   -   T3   w
 methyl acetate   -99   57   2.56   -10   3.1   16   95   500   475   -   T1   IIA
 methyl acetoacetate   170   4.0   67   -   -   -   -   280   -   T3   IIA
 methyl acetylene   -   -23   1.4   -   1.7   -   -   -   -  t  w
 methyl aaylate   < -75   80   3.0   -3   2.8   25   100   895   -   -  t  w
 methyl cydobutane   -   -   -   -   -   -   -   -   -   -  t  IIA
 methyl cyclohexane   -127   101   3.38   -4   1.15   6.7   45   -   260   -   T3   IIA
 methyl cydohexanol
 -38   168   3.95   68        295     -    T3      IIA
 methyl cydopentane   -   72   2.9   < -7   -   -   -   -   -   -  t  IIA
 methyl formate   -100   32   2.07  < -20   5   23   120   570   450   -   T1   IIA
             -
                       -
 methyl methacrylate   -   -   -   (10)   -   -   -   -  t  IIA
 2-methyl   -108   107   2.55   -   1.7   10.9   -   -   408   -   (n)   IIA
 propan-1-31
   122   123   124   125   126   127   128   129   130   131   132