Page 203 - Electrical Installation in Hazardous Area
P. 203

Design philosophy for electrical apparatus for explosive atmospheres  1 67


                  encapsulation of  the electrical circuits, and pressurization of  the enclosure
                  containing the electrical circuits with non-flammable gas.



                  Oil immersion (symbol ‘0’)
                  In  this protection  concept (type of  protection) the  electrical components
                  are immersed in oil within their enclosure, thus preventing access of  the
                  explosive atmosphere. It is dealt with in detail in Chapter 9. There are limi-
                  tations on the type of  oil which may be used and requirements to ensure
                  the security of  the oil within the enclosure, so that  the electrical circuits
                  remain immersed. The technique is considered as suitable for Zone 2 only,
                  at present, within the UK but is used in more hazardous areas in other coun-
                  tries. This is likely to change in the not-too-distant future (see Chapter 9)
                  and will be the protection concept permitted in Zone 1.



                  Encapsulation (symbol ‘m’)

                  This protection concept is dealt with in detail in Chapter 9. Again, the explo-
                  sive atmosphere and electrical circuits are separated from one another, this
                  time by  encapsulating (potting) material. The types of  material used  are
                  defined and the encapsulated block is arranged so that surfaces presented
                  to the outside are hard enough to give protection. The technique is consid-
                  ered as suitable for both Zone 1 and 2.


                  Pressurization (symbol ‘p’)

                  This protection concept is dealt with in detail in Chapter 11. In this tech-
                  nique the explosive atmosphere is kept out of  the equipment enclosure by
                  pressure of  air or inert gas. Air is normally used as there are asphyxiation
                  problems with inert gas. Because the protection is by a gas (air) it is almost
                  always necessary to provide ancillary equipment to ensure that the air pres-
                  sure is maintained in spite of  small leakages, which are almost certain to
                  occur. Because of  this  the  technique  almost  always requires a  pressure-
                  control system, together with a purge system to ensure that on start-up any
                  internal explosive atmosphere is removed, and  this gives added compli-
                  cation which must be set against its added flexibility because of  the ease
                  of  depressurizing for  repair. The  technique is considered as suitable for
                  both Zone 1 and 2 or only Zone 2,  depending upon the pressure-control
                  systems used.


                   7.2.2 Prevention of sparking (criterion b)

                  There  is  only  one  formal protection concept which  is  suitable for  both
                  Zone 1 and 2 in this area.
   198   199   200   201   202   203   204   205   206   207   208