                                      Physical Description of HVAC Pumps

                    116   HVAC Pumps and Their Performance










































                    Figure 5.7 Double-suction axially split, volute pump. (Courtesy Patterson
                    Pump Company, A subsidiary of The Gorman-Rupp Company.)

                    provide semiopen impellers. These impeller configurations are shown
                    in Fig. 5.8a and b.
                      Turbine-type pumps with enclosed impellers and bowl rings usually
                    offer the highest sustained pump efficiency due to the ability to con-
                    trol more closely the amount of bypassing that occurs between the
                    impeller and the bowl. Semiopen impellers must be checked periodi-
                    cally for the right clearance between the impeller and the bowl. The
                    correct clearance between the impeller and the bowl is called the lat-
                    eral setting. This setting can be accomplished by adjusting the top
                    drive coupling of a vertical, hollow-shaft motor or by a special spacer
                    coupling below a vertical, solid-shaft motor.
                      2. Mixed flow. Mixed-flow pumps are used on high-capacity,
                    moderate-head applications; they are found in the HVAC industry on