Page 268 - Handbook of Electrical Engineering
P. 268

HAZARDOUS AREA CLASSIFICATION      253

                 The definitions in the USA differ slightly by the use of ‘Class’ rather than ‘Group’.

                 The grouping code influences the design of jointed and mating surfaces and shaft seals, because
           the gases in different groups have different explosive and burning characteristics e.g. speed of flame
           propagation, rate of rise of explosive pressure. Hence the grouping codes influence the physical design
           of enclosures. The gases hydrogen and acetylene for example are notably difficult gases to cater for
           in designs. Hydrogen is often encountered in the oil industry, and acetylene in the chemical industry.


           10.4 HAZARDOUS AREA ZONES
           In the European and UK standards the term Zone is used for hazardous areas, whereas the term
           Division is used in the USA. In practice the end result of selecting appropriate equipment for a Zone
           or Division is usually very similar. There are a few subtle differences, especially when selecting
           electric motors. The zonal definitions vary in wording from one document to another but the essential
           elements are as follows.


           10.4.1 Non-hazardous Area

           In the earlier period the term Safe Area tended to be used to mean an area that was deemed to be
           completely free of potential hazards. As with many technologies their terms and definitions take on
           slight changes as time passes, usually because of the feedback effect of experience. In this way the
           term Non-hazardous Area seems to have superseded Safe Area. (Curiously the zonal numbering is
           in opposite sense to the severity of hazard, zero is the worst and 2 is the least, as discussed below.)



           10.4.2 Zone 2 Hazardous Area

           The lowest non-zero risk of hazard is to be found in a Zone 2 area. In a properly designed and
           maintained plant the occurrence of leakage of flammable gas, vapour or volatile liquid from within
           the vessels, tanks, piping, valves, seals, pumps, compressors and the like is accepted as being unlikely
           but possible. The possibility is deemed to exist when a fault develops in the equipment e.g. a flange
           gasket fails, a pipe fractures. These occurrences come under the category of ‘wear and tear’. It
           is possible that a leakage may result from some mal-operation e.g. a heavy object is accidentally
           dropped onto equipment that contains a hazardous fluid e.g. a pipe, which either pierces the metal or
           loosens a joint. These occurrences may be categorised as ‘accidental’ causes, and can be considered
           as being statistically low, hence the risk of explosion is also low. They may be considered unlikely
           to occur over a long period of time (months, years) or if they do then the time period will be short
           (up to 10 hours per year, see Reference 1).


           10.4.3 Zone 1 Hazardous Area

           A higher risk of hazard than that applicable to a Zone 2 area, is found in a Zone 1 area. Again it
           can be considered that the plant is properly designed and maintained. However, some parts of the
           plant are more prone to leakage than others, some types of seals used in rotating shafts of pumps
           and compressors, discharges from safety valves, some methods of venting gases and vapours, some
           types of open drains for volatile liquids. Hence leakage may be considered likely to occur some time