Page 67 - Handbook of Energy Engineering Calculations
P. 67

external low-cost, finned-tube heat exchanger, Fig. 6, where waste heat from
               the gas turbine is recovered.



























                          FIGURE 6 Gas-turbine heat-recovery finned-tube heat exchanger is

                     simple and needs no elaborate controls. (Power.)

                  When high-pressure feedwater heaters are shut off, steam flow through the
               intermediate- and low-pressure turbine sections increases and becomes closer
               to  the  full-load  design  flow.  The  reheat  expansion  line  moves  left  on  the

               Mollier chart from its derated position, Fig. 7. With steam flow closer to the
               design value, the exhaust losses per pound (kg) of steam, Fig. 8, are lower
               than at the derated load.