Page 31 - Hybrid-Renewable Energy Systems in Microgrids
P. 31

16                                  Hybrid-Renewable Energy Systems in Microgrids

          Table 1.4  Parameter of the studied system


           Generator  P nom    V L-L  (kV)  Xd    Xd′        Xd″       Xq
                      (MVA)
                    5          13        1.790    0.355      0.275     1.660
                    Xq’        Xq”       Tdo′     Tdo″       Tqo′      Tqo″
                    0.57       0.275     7.9      0.032      0.41      0.055
           Step-up   P nom     V prim  (kV)  V s  (kV)  R1,R2 (pu)  L1,L2 (pu)  –
             trans-   (MVA)
             former  5         13        25       0.08/30    0.08      –
           Trans-   r1 (Ohms/  r0 (Ohms/  l1 (H/  l0 (H/km)  c1 (F/km)  c0 (F/
             mis-     km)        km)       km)                           km)
             sion   0.1153     0.413     1.05e-3  3.32e-3    11.33e-9  5.01e-
             lines                                                       9
           PV       P nom      V prim  (V)  V s  (kV)  R1,R2 (pu)  L1,L2 (pu)  –
                    1 MW       260       25       0.001      0.03      –
           Wind     P nom      Nominal   Wind     Inertia    Maximum   V L-L
                                 DC bus    speed    constant   pitch     (V)
                                 voltage            H (s)     angle
                                 (V)                          (degree)
                    1 MW       1150      15 m/s   4.32       27        575
           Step-    P nom      V prim  (kV)  V s  (kV)  R1,R2 (pu)  L1,L2 (pu)  –
             down     (MVA)
             trans-  1.2       575       25kv     0.025/30   0.025     –
             former
           Load     Active     Reactive   Voltage   –        –         –
                      power      power     (kV)
                      (MW)       (MVar)
                    6          1         11       –          –         –
           Load     P nom      V prim  (kV)  V s  (kV)  R1,R2  L1,L2   –
             trans-   (MVA)
             former  8         25        13       0.08/30    0.08      –



         7.1  Load generator with PV only

         7.2  Load generator with wind only
           It can be seen from the Figs. 1.7–1.9 that wind farm can improve the post-fault
         transients of the PV farm. It can be seen from the Figure 1.10 and Figure 1.11 that PV–
         wind combination gives smoother response than the PV-only configuration. Therefore
         improved performance in voltages is visible at generator terminal, bus, load, and PV
         farm terminal in a hybrid (PV–wind) MG system compared to PV-only MG under the
         disturbance condition. However, wind-only configuration performs better than PV–
         wind combination under the studied disturbance scenario.
   26   27   28   29   30   31   32   33   34   35   36