Page 692 - Industrial Power Engineering and Applications Handbook
P. 692

~    ~~
             I                2                 3                 4                5                 6                 7
             I1  Effect  of  leakage  on
               performance:
             (i)  Operating safety   Since the oil is filled at atmospheric pressure, there is  Not  applicable   Not  applicable   (i) Generally, the use of   Generally a safe
                              generally no leakage                                                   SF,  is safe, inhaling is   equipment. But in the
                                                                                                     poisonous.  If there is a   event of  vacuum leakage
                                                                                                     leakage it would be   which, although remote,
                                                                                                     dangerous. SF,  itself is   may cause a fire hazard
                                                                                                     non-toxic,  but decom-   and X-rays. X-ray
                                                                                                     posed  SF,  is moderately  warning and proper
                                                                                                     toxic and must be   shielding may be
                                                                                                     handled under controlled  essential
                                                                                                     conditions. Training and
                                                                                                     guide-lines  are essential
                                                                                                     for personnel working
                                                                                                     on such equipment. Site
                                                                                                     data collected  from
                                                                                                     various sources,
                                                                                                     however, suggest a
                                                                                                     leakage rate of  less than
                                                                                                     0.1 % per annum
             (ii)  Dielectric strength  Not applicable   Not  applicable   Not applicable   Not applicable   Still high   Zero
             (iii)  Intempting capacity  Not applicable   Not  applicable   Not applicable   Not applicable. But if the  In the event of  a   In the event of a
                                                                                   leakage is in the compres-  leakage, the breaker will  leakage, the breaker will
                                                                                   sed air supply system, the  still be in a position  to   not be in a position to
                                                                                   breaker may not interrupt  interrupt the normal   interrupt even normal
                                                                                   on fault, depending upon  currents   currents
                                                                                   the air pressure the system
                                                                                   is  able  to  maintain  on  a
                                                                                   leakage
             12  Fire hazards   Generally, oil is fire hazardous, but not prone to it   They may be rated as more fire hazardous than a   Arc formation and extinction  takes place inside a
                              unless the dielectric strength reaches a very low   BOCB or MOCB in view of arc formation taking   sealed chamber, thus emitting no gases or vapoura
                              level and the medium itself becomes  conducting.   place in the open, although under controlled conditions.  to the atmosphere, which may be a cause of fire
                              Nevertheless, they are not suitable at locations   They are not suitable for installations prone to fire   hazard. They are the most appropriate choice for
                              which are fire hazardous. Normal make or break,   hazards, unless the sub-station  or the control room   such areas
                              even on  fault, may only deteriorate the quality of'   where they are installed is isolated from the area of
                              oil, but yet not make it fire hazardous,  unless as   hazards (Section  7. I I).  They are generally  suitable
                              noted above                        for all other areas
             13  Noise level   Quiet operation   Quiet operation   Except during an   Thunderous noise during  Quiet operation   Quiet operation
                                                                 interruption, it has quiet   an interruption, because of
                                                                 operation         air blast. The intensity can
                                                                                   be controlled by providing
                                                                                   silencers