Page 307 - Solutions Manual to accompany Electric Machinery Fundamentals
P. 307
Since there are 60 coils in each phase and 8 turns per coil, all connected in series, there are 480 turns per
phase. The resulting voltage is
V 2N P k p k d f e 2 480 turns 0.951 0.962 60 Hz
V 117 , 061
The phase voltage of this generator must be 13 8 . kV / 3 7967 V , so the flux must be
7 967 V
. 0 068 Wb
117,061
(b) The machine’s winding factor is
k w k p k d 0.951 0.962 0 . 915
301