Page 269 - Practical Power System and Protective Relays Commissioning
P. 269

Protection Relays Chapter | 18  265


                Radio links;
                Few used in the past;
                Optical fibers.
                The most recent system is to transfer the current signals and all tripping
             and protection accelerating signals along of fiber optic between the two ends
             of the line. Refer Fig. 18.10.8.
















             FIGURE 18.10.8 Line differential protection with a fiber-optic communication channel.



                In recent relays there are two bias constant zones in its operating
             characteristic, the first one for low fault currents that need less bias and
             the second one for high fault currents that need more bias as shown in
             Fig. 18.10.9.





















             FIGURE 18.10.9 Stabilization characteristic of fiber-optic line differential protection.