Page 136 - Solar Power in Building Design The Engineer's Complete Design Resource
P. 136
106 INTRODUCTION TO SOLAR POWER SYSTEM DESIGN
Isc (short-circuit current) 5.30 A
Imp (maximum peak current) 4.90 A
Maximum system voltage (V dc) 600 V
Input Assumptions
Inverter model 75 kW, 480 V ac
PV module SolarWorld AG SW 175 mono
Temperature scale Fahrenheit
Minimum ambient temperature 25
Maximum ambient temperature 90
Mounting method Ground mount/tilt
CEC or STC module power STC (standard test condition)
Optimum array derating coefficient 0.8
Voltage drop in array wiring 1.5
Resulting Design Parameters
Ideal number of series modules (strings) 11
Nominal Vmp w/11 series modules (V dc) 387
Minimum number of modules 11
Maximum number of modules 11
Maximum allowed number of modules 560
Maximum number of series of module strings 48
Inverter Output
Continuous ac power rating 75 kW
AC voltage (V ac line—line) 480 V, 3 phase
Nominal ac output current 91 A
Maximum fault ac output current/phase 115 A
Minimum dc input voltage 330 V dc
Maximum dc input voltage 600 V dc