Page 294 - Sustainable On-Site CHP Systems Design, Construction, and Operations
P. 294

Operation and Maintenance Services      267


             The HRSG may also have a separate superheater section and an economizer. Like any
             boiler, it is very important to maintain a reliable water conditioning system to control
             scale build up. The CHP plant operators must test and chemically treat the HRSG water
             on a daily basis.
                Further, like any boiler, the HRSG must be opened for cleaning and inspection once
             a year. There are many installations where air quality regulations require a significant
             reduction in exhaust emissions. In these cases, catalysts are often installed in the HRSG.
             The catalyst sections should be visually inspected and a section should be removed
             and tested in a laboratory to determine the remaining service life. The NO  catalyst
                                                                              x
             requires ammonia injection and the delivery and injection system must be cleaned and
             inspected periodically.
             STG
             In addition to the schedule in Table 16-1, the steam turbine internals must also be
             inspected periodically. The frequency of the inspection depends on the steam conditions
             and operation, but, if possible, should not exceed 3 years (see Table 16-2). It is important
             to check the lube oil system for proper level and quality before starting the unit and
             while it is in operation.

             Steam Turbine Chillers and Absorption Chillers
             Maintenance requirements on steam turbine–driven centrifugal chillers are identical to
             the STG on the turbine side. The chiller end must be leak checked and maintained with
             the proper amount of refrigerant. The evaporator and condenser heat exchangers must
             be cleaned and inspected at least once a year. Condensing water must be provided and
             maintained at the proper temperature to achieve the overall efficiency of the chiller. If a
             cooling tower is used, the operator must maintain an effective water conditioning and
             chemical treatment program to protect the condenser tubes from fouling and corrosion.
                Maintaining absorption chillers is unique in that it has no internal moving parts. A
             constant flow of water through the evaporator and through the condenser will main-
             tain a stable heat transfer process within the unit. Since steam or hot water is used to
             separate the water and lithium bromide in the generator section, the heat transfer in the
             condenser is greater than with centrifugal units, therefore the cooling water supply is
             even more important.


             Plant Auxiliaries
             A CHP plant has a number of auxiliary systems that support the CTG, engines, genera-
             tors, and HRSG, or hot water heat recovery unit. Most of the equipment is common to



               Maintenance
               Annual permit inspection
               Open all ducts—inspect, for loose insulation, all internal panels, catalyst and clean
               Drain and open mud and steam drums and clean
               Replace safeties (send out existing for recertification)

             TABLE 16-1  Typical HRSG Maintenance Schedule
   289   290   291   292   293   294   295   296   297   298   299