Page 175 - The Engineering Guide to LEED-New Construction Sustainable Construction for Engineers
P. 175

LEED Ener gy and Atmospher e     153


                           LEED 2009 Percent Reduction      LEED 2.2 Percent Reduction
               Points    New Buildings  Existing Building  New Buildings  Existing Building
               Required       10               5        0              0
               (EAp2)
                   1          12                8       10.5 (required)  3.5 (required)
                   2          14              10        14 (required)  7 (required)
                   3          16              12        17.5           10.5

                   4          18              14        21             14
                   5          20              16        24.5           17.5
                   6          22              18        28             21
                   7          24              20        31.5           24.5
                   8          26              22        35             28
                   9          28              24        38.5           31.5
                  10          30              26        42             35
                  11          32              28        −              −
                  12          34              30        −              −
                  13          36              32        −              −
                  14          38              34        −              −
                  15          40              36        −              −
                  16          42              38        −              −
                  17          44              40        −              −
                  18          46              42        −              −
                  19          48              44        −              −
               19 + 1 EP      50              46        −              −

             TABLE 4.1.1  Table of Point Differences between Version 2.2 and Version 2009, EAc1 Option 1
             Based on Percent Reductions in Energy Uses from a Baseline



                OR
                OPTION 2 — PRESCRIPTIVE COMPLIANCE PATH (4 points in version 2.2, 1 point in
                version 2009)
                Option 2 is based on ASHRAE Advanced Energy Design Guides for various uses. In version
                2.2 only the Small Office Building pathway was available, but version 2009 includes two
                additional pathways for Small Retail Buildings (Path 2) and Small Warehouses and Self
                Storage Buildings (Path 3), based on the  2006 and  2008  applicable ASHRAE Advanced
                Energy Design Guide, respectively. The requirements are listed in Table 4.0.0 and are both
                required as the EAp2 Minimum Energy Performance prerequisite and available as one point
                for EAc1 in the 2009 version of LEED-NC. For small office buildings LEED 2.2 required to: