Page 105 - Uninterruptible Power Supplies
P. 105

Additional Information Relating to the Standby Supply Installation
                     Additional Information Relating to the Standby Supply Installation  103


            and many other harmonic currents producing an rms total harmonic
            distortion of 110 percent. In three-phase systems triplen harmonic cur-
            rents have zero phase sequence and become additive in the neutral
            return path. In a distribution system supplying a large computer
            installation the neutral current can be large and can exceed the phase
            current; the system should be designed to allow for this. This statement
            applies whether the load is being supplied from the standby supply or
            from the normal supply.
              Small computers may be connected directly to the supply, and while
            most computers of importance will be supplied from an uninterruptible
            power supply, they may on occasions be connected directly to the nor-
            mal or the standby supply when the uninterruptible power supply is
            operating in bypass mode. Where standby power generation is at low
            voltage, the triplen harmonic current components will appear in the
            generator neutral and can cause overheating. If the total neutral cur-
            rent is likely to exceed say 15 percent of rated current, the generating
            set manufacturer should be advised.

            Fluorescent and Discharge Lighting
            These are nonlinear loads taking a current rich in odd harmonics. BS
            EN/IEC 61000-3-2 allows a third harmonic of up to 30 percent. The
            same problems arise with neutral currents as are described for com-
            puter loads in the preceding subsection.

            Cyclically Varying Loads
            A load such as a rotating radar aerial will vary cyclically at a regular
            rate due to the aerial’s rotation and the more or less static direction of
            the wind. If the regular rate of variation is comparable to the natural
            frequency of response of the engine governor, continuous hunting about
            the mean speed may occur. Continuous motion of the governor parts
            and linkages can lead to premature wear and to lost motion in the fuel
            control mechanism. Increasing the speed of response of the governor
            may lead to instability, and reducing the speed of response may result
            in the frequency not remaining within specification. The generator set
            manufacturer should be aware of a significant load of this nature at an
            early stage of the contract.


            Motors
            Any large motors in the load will affect the supply voltage during start-
            ing. An induction motor will take a current of six or seven times its
            rated current at a power factor of say 0.15 when started direct on line.
            A squirrel cage motor taking a starting current equal to the generator



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   100   101   102   103   104   105   106   107   108   109   110