Page 42 - Uninterruptible Power Supplies
P. 42

Standby Power Generating Sets
            40   Chapter One


            Monitoring the Status of the Normal Supply
            Monitoring the voltage and frequency of the normal supply should be
            at a point upstream of the normal supply changeover contactor or cir-
            cuit breaker. If it is at a point downstream of the changeover device the
            restoration of the supply cannot be monitored. In addition the logic
            should be such as to prevent the generator attempting to supply the
            load in the event of the normal supply having tripped on fault or over-
            load. This can be achieved by connecting an auxiliary contact on the
            protective device which passes information to the control module. It is
            usual to monitor the three phase voltages, any phase unbalance, and
            the frequency.


            Automatic Starting and Shutdown
            Sequences
            The automatic start sequence should commence after the expiry of an
            adjustable delay, (say 0–10 seconds), initiated by the normal supply
            mains monitor. The delay avoids spurious starting during a transient
            loss of the normal supply, and is particularly useful if the supply sys-
            tem includes any autoreclosing switchgear.
              The automatic shutdown sequence is initiated either by the control
            system or by one or more of the engine safety shutdown devices. Some
            engines (particularly the larger units) are arranged to continue run-
            ning off load for 5 or 10 min in order to allow heat to be removed from
            the cylinder block, heads, and pistons before finally shutting down.
            This procedure is not applicable to alarm shutdown signals such as
            overspeed, but the omission of the light load running period can lead to
            boiling of the cooling water at engine hot spots.

            Operating the Switching Devices
            After a failure of the normal supply the generating set should be auto-
            matically started, and the switching sequence to load the set com-
            pleted, after which the standby supply remains in use until a shutdown
            command is given.
              The switching sequence may involve three or more functional devices,
            which may be circuit breakers or contactors. They are the supply change-
            over devices, the load-shedding device(s), and any step load limiting
            devices necessary to apply the load to the set in two (or more) steps or
            stages. It is important that any load-shedding and step load limiting
            devices are open before the standby supply changeover device is closed.
              If the switching devices are circuit breakers, the control system
            should arrange for their operation to be delayed until the generating
            set is up to speed and ready to accept load. This avoids unnecessary cir-
            cuit breaker operation—if the normal supply is restored before the



         Downloaded from Digital Engineering Library @ McGraw-Hill (www.digitalengineeringlibrary.com)
                    Copyright © 2004 The McGraw-Hill Companies. All rights reserved.
                      Any use is subject to the Terms of Use as given at the website.
   37   38   39   40   41   42   43   44   45   46   47