THE DESIGN AND CONSTRUCTION PROCESSES 1-13

          TABLE 1-3
          Guidance for minimum equipment and process reliability for water treatment
          Component                 Recommendation
          Source
          Surface water
           Capacity                 Meet a one-in-50-year drought with due consideration for multiple year
                                     droughts
           Intake structures         Where intake tower is used, provide two independent intake cells, each
                                    with three intake ports at different elevations
           Pumps                     Minimum of two; meet the maximum day demand with one unit out of
                                    service
          Groundwater
           Capacity                 Equal or exceed maximum day demand with largest producing well out
                                    of service
           Wells                    Minimum of two
          Treatment

          Rapid mix                 Minimum of two; meet the maximum day demand with one unit out of
                                    service
          Flocculation              Minimum of two; meet the maximum day demand with one unit out of
                                    service
          Sedimentation             Minimum of two; meet the maximum day demand with one unit out of
                                    service
          Disinfection              Minimum of two; meet the maximum day demand with one unit out of
                                    service
          Power                     Provide primary transmission lines from two separate sources or
                                    standby generator
          Finished water storage

          Capacity                  Equal to the average day demand when fire protection is not provided
                                    Meet domestic demand and fire flow demand where fire protection is
                                    provided
          Distribution
          High service pumps        Minimum of two; meet the maximum day demand with one unit out of
                                    service
          System pressure           Minimum of 140 kPa at ground level at all points in the system
                                    Nominal working pressure should be 410 to 550 kPa and not less than
                                    240 kPa
          Sources: Foellmi, 2005; GLUMRB, 2003.