Page 290 - Well Control for Completions and Interventions
P. 290

Well Kill, Kick Detection, and Well Shut-In                  283


              Initial pump pressure ðmechanical tubing burst limitÞ 5 tubing burst limit
                 tubing hydrostatic pressure at packer



              7 Calculate maximum pump pressure (tubing burst mechanical limit)
              at the end of the kill
              At the end of the kill, the highest pump pressure than can be applied at
              the surface is tubing burst limit, minus the HP of the kill fluid in the
              tubing at packer depth. This is a worst-case assumption, and makes no
              allowance for the HP in the annulus.
               Final pump pressure ðmechanical tubing burst limitÞ 5 tubing burst limit
                 tubing hydrostatic pressure at packer




              7.4.3 Bullhead procedure
              If a rig is on location, the mud pumps are normally used to kill the well.
              However, a bullhead kill can be carried out using a mobile pumping unit
              before the rig arrives on location. This can bring about significant cost
              savings.
                 Outline procedure:
              1. Hook up a temporary treating (Chiksan) line from the pumping
                 equipment to the Christmas tree. Fluid is usually pumped via the kill
                 wing or swab cap. The treating line should be fitted with non-return
                 valves close to the tree, as well as a pressure relief valve. The line must
                 be secured.
              2. If there are holes in the tubing and simultaneous injection of kill fluid
                 is required, or if pressure needs to be applied to the annulus to reduce
                 tubing burst loading, a second temporary line will need to be made
                 up to the production (A) annulus side outlet valve. The line should be
                 fitted with a non-return valve close to the wellhead, as well as a pres-
                 sure relief valve. The line must be secured.
              3. The lines should be tested before pumping begins. Test pressure must
                 exceed the maximum anticipated pump pressure by a suitable margin,
                 typically a 10% excess, or 500 psi, whichever is greater.
              4. Begin to pump kill fluid at a rate high enough to push produced fluids
                 in the tubing back into the formation. In practical terms, the pump
                 rate will be as high as possible whilst remaining below the fracture
   285   286   287   288   289   290   291   292   293   294   295