Page 183 - Advanced Design Examples of Seismic Retrofit of Structures
P. 183

Example of an RC Building Retrofitted by RC Shear Walls Chapter  3 175










































             FIG. 3.36 Shear forces in the shear wall W2 ( 10  1  kN/m).

             aim of these controls is determination of the capacity adequacy of the soil and
             foundation.

             Loads Combinations For controlling the soil pressure and settlement, the load
             combination D+L is used. The load combination 1.2D+1.6L is utilized for con-
             trolling the foundation capacity. ACI 318 [5] is used in this part.

             Controlling the Soil Pressure Under Foundation Based on the geotechnical
             consultant recommendation, the modulus of soil reaction in vertical direction
                                  7
                                       3
             (K s ) is assumed as 2.2 10 N/m . The results of Fig. 3.37 indicate the soil pres-
             sure in the majority of locations is smaller than the allowable soil stress
             q a ¼0.35MPa. It is noteworthy that the equipment load is assumed to be 4kPa.
             Controlling the Soil Settlement The results of Fig. 3.38 show the soil settle-
             ment in the southern and the northern parts are 1.5cm and 1.0cm, respectively,
             which are smaller than the allowable settlement of 5.0cm.