Page 225 - Alternative Energy Systems in Building Design
P. 225

DEMAND-SIDE ENERGY MANAGEMENT AND CONTROL    201


                       Intelligent control During the peak utility demand periods, the energy-management
                       system periodically turns air-conditioning compressors off to control the number of
                       compressors operating at any one time. Before turning a compressor off, the system
                       looks at the setpoint temperature and the room temperature and selects the systems
                       that have been running the longest and closest to the setpoint or satisfying the call for
                       cooling. The software within the energy-management system also considers the priority
                       of each system, the amount of temperature rise allowed for each system, and the number
                       of systems that are allowed to operate at any one time.


                       Energy conservation The energy-management systems conserve energy by mini-
                       mizing the amount of time the HVAC systems operate and by monitoring the perform-
                       ance of the HVAC systems to ensure that all components are operating efficiently and
                       together in the most efficient mode for the application.

                       Time/temperature programming Energy-management systems in general can
                       be programmed so that each day may have a different time and temperature schedule
                       with up to four temperature changes per day for cooling and heating. Each program or
                       schedule can use different temperatures for cooling and heating.
                         The energy savings achieved by raising the cooling setpoint 5°F for an 8-hour period
                       are widely stated as 15–30 percent depending on the geographic location. Similarly, a
                       10°F setback in heating for an 8-hour period can reduce energy consumption by another
                       7–15 percent depending on geographic location.

                       Just-in-time temperature programming The energy-management system
                       monitors the outdoor temperatures and computes when it should turn on the heating
                       or cooling to ensure that the temperature programmed will be reached at the proper
                       time and not too early. Starting a heating or cooling call 30 minutes early can increase
                       the energy consumption by 6 percent in 8 hours of call time.

                       Vacation/holiday programming The energy-management system can be pro-
                       grammed at the beginning of the year for up to 12 vacation or holiday periods. These
                       days are entered by date to program holiday temperature settings for both heating and
                       cooling. In a commercial application, this results in significant energy savings.

                       Alarm reporting The energy-management system can be programmed to report
                       alarm conditions of peak demand or energy consumption. The alarms will be reported
                       locally on the master control unit or PC and dialed out to report the alarms to an offsite
                       PC for notification and action.

                       Energy conservation by improved system efficiency The energy-management
                       system conserve energy by operating the HVAC system in its most efficient mode by
                       monitoring output or supply-air temperature, return-air temperature, room temperature,
   220   221   222   223   224   225   226   227   228   229   230