                                                                Refrigeration Systems                                      343






























































                     Figure 11-37. Gas horsepower for two-stage propylene refrigeration system. (Excerpted by special permission: Mehra, Y. R. Chemical Engi-
                     neering, Jan. 15, 1979. ©McGraw-Hill, Inc., New York. All rights reserved.)




                         Step 4a. Evaporator volume:
                                                                                     3
                                                                           Now assume  / 4 in. O.D. tubing, 16 ft long.
                     The load   q   1,000 tons   12,000,000 Btu/hr.
                                                                                           4,000
                     Assume an overall heat transfer coefficient.           No. of tubes               1,280
                                      2
                     U   200 Btu/(hr) (ft )(°F) for brine cooling.                       16     0.196
                     Also assume  t   15°F.
                                                                           The approximate tube bundle diameter for tubes layed out on tri-
                                    q    12,000,000                        angular pitch can be calculated from
                      Therefore: A                  4,000 ft 2
                                    t U  15     200                                                      (Text continues on page 348)