Page 184 - Applied Photovoltaics
P. 184

Figure 9.5. Loss-of-load-probability (LOLP) as a function of days of storage
                                 (©1987 IEEE Jones & Chapman).


                          From Fig. 9.5, it can be seen that an array sized to meet the load, in conjunction with
                          one day’s battery storage, gives an average availability (1 – LOLP) of approximately
                          94%. This value should be taken as the upper bound on the fraction of the energy in a
                          hybrid system that can be economically displaced by the photovoltaic array. In
                          reality, to make use of all the photovoltaic-generated power in summer, the array size
                          needs to be a little less than that needed to supply the energy requirements of the load.
                          The implications of this on photovoltaic array sizing and tilt angle are that:
                              x  An increased tilt (i.e. greater than the latitude) gives more uniform all-year-
                                 round generation, but at the expense of total annual output.
                              x  It is good policy to select the array size and tilt angle together, aiming for the
                                 photovoltaic generation on a clear summer day to be equal to the load.
                              x  The array generation should not be too much below the load or else the diesel
                                 will be required semi-continuously to supply the difference. (Not everyone
                                 agrees with this aim.)
                              x  As a guide, do not consider a hybrid system unless the inclusion of
                                 photovoltaics offsets at least 30% of the estimated diesel’s operation and
                                 maintenance costs (Jones & Chapman, 1987). (Refer to the hybrid indicator
                                 of Chapter 7.)
                              x  The system design should provide for infrequent use of the diesel, but for
                                 relatively long periods of time on each occasion used, at close to full load.
                              x  It is preferable for the array not to meet the load fully so as to optimise the
                                 system cost and ensure the generator will be operated for a reasonable length
                                 of time every two weeks.
                              x  The system voltage should be selected in accordance with the inverter
                                 characteristics and requirements. In general, this involves limiting the DC
                                 current to 100 A maximum.







                                                                                                171
   179   180   181   182   183   184   185   186   187   188   189