Page 80 - Boiler Operator’s Handbook
P. 80

Boiler Plant Operations                                                                              65


               what you have to do.                                 fire purge it twice to get all that fuel out of there before
                    I say you can’t be timid or quick in this operation  trying again.
               because you don’t want to create a flammable mixture     Use the purge period to think about why you didn’t
               that doesn’t light right away. If you open the manual  get a fire. It might be because the gas piping was full of
               valve too slowly you will allow so little fuel in that the  air and you forgot to purge it. It might be that you simply
               mixture at the burner will always be too lean to burn.  forgot to start the oil pump (in which case, why did the
               However, the fuel can settle or rise and accumulate to  low oil pressure switch not prevent an attempt at igni-
               create a mixture that’s just right, waiting for you to finally  tion?) or you forgot to open a fuel or atomizing medium
               get ignition. If you open the valve rapidly you can shoot  valve. Maybe you saw a little light burning indicating
               right past the point where the mixture is right and into  you didn’t have enough fuel or a lot of smoke indicating
               a fuel rich condition that won’t burn; that only happens  you had too much so you can adjust the controls accord-
               if the controls admit too much fuel, and they have half a  ingly. One problem with steam and air atomized burners
               chance on an initial start-up. That fuel in its rich condi-  is not enough fuel but it’s not apparent because the steam
               tion can mix with some air in the furnace to produce a  or air is breaking it up. Make some corrections then, after
               flammable mixture and accumulate in preparation for an  a purge, try again until you get it going.
               explosion, suddenly lighting when you don’t expect it.     Now for an operation that many service techni-
                    If you’re going to be the one operating that valve  cians fail to do, mainly because it can take some time and
               do a few practice runs before doing it for real and time  several light-offs, do a pilot turndown test. It’s a process
               yourself. You should operate a plug valve or butterfly  where you prove to yourself that, if the ignitor fire has
               valve from closed to open in approximately five sec-  decayed to the point where it can’t light the main burner,
               onds. That gives you enough time to stroke through  the scanner will prevent an attempt at ignition on a faulty
               all the potential mixture conditions within the trial for  pilot. Throttle the gas supply to the ignitor until you note
               ignition period without going so fast that you miss the  a drop in the flame. Make sure the ignitor can light the
               proper point of ignition. When lighting off on oil you’re  main flame. Continue dropping the pressure and check-
               usually using a multiple turn valve that’s really open  ing to be sure the main flame ignites. If, during the pro-
               enough for low fire in two turns so practice getting it  cess, the scanner fails to detect the ignitor flame and the
               two turns open in five seconds. Also train yourself to  Burner Management locks out the test is complete.
               close the valve at the same speed.                       That seldom happens, what usually happens is
                    Keep in mind when you’re operating that valve  the ignitor fails to light the main fire. Now you have
               that there is a delay involved; the fuel has to displace  to repoint or orifice the scanner so it will not detect the
               the air in the burner piping and burner parts before it  ignitor flame when it isn’t adequate to light the main
               can enter the furnace and start mixing with the air. An  burner. Matching that scanner position or orificing so it
               assistant watching the fuel gauge can read off pressures  also allows reliable detection of the main flame can fre-
               to you so you can get an idea of where you are. You want  quently be a problem. You have to do it, however, or the
               to stop opening the valve the instant you see that main  system can be forced to repeatedly attempt light-off of
               fire light and be prepared to close it a little or open it a  a main flame with an inadequate ignitor and the results
               little more depending on your perception of the fire. If  have been very devastating in some installations.
               the fire is bright and snappy, an indication that it’s air     Now that you have managed to light a main burn-
               rich, you should open the valve more. If the fire is lazy,  er you want to establish proper firing conditions so you
               rolling, and smoking to indicate it’s fuel rich you should  can repeat them for every light-off. If you managed to
               close down on the valve.                             open the manual valve completely without changing the
                    If you didn’t get a fire then allow a full purge of  condition of the fire you’re past the need to balance the
               the boiler. It’s not uncommon to have several attempts  manual valve and controls. If not, then note the burner
               at starting that first fire. My service technicians were  pressure and close down on the main fuel control valve
               artists and knew what they were doing but they always  a little (or adjust the minimum pressure regulator) then
               upset me by shortening the purge time so they could  open the manual valve a little to restore the pressure and
               get back to trying the main burner faster. Please don’t  repeat the process until the manual valve is wide open.
               do that! Every missed fire leaves an accumulation of  Once you know what the proper conditions for start-up
               fuel in the boiler that can produce a healthy explosion  are the only reason for operating the manual valve is
               when it’s lit by the next operation of the ignitor. Always,  when you question the ability of the system to repeat
               please, allow for a full purge; and …if you saw a smoky  those conditions. You should get a smooth light-off ev-