Boiler Plant Operations                                                                              87


               refractory so some minor refractory damage may incur     Like the old rule of thirds (page 111) I recommend
               if a standby has to be brought on line immediately but  you operate your plant so one boiler has half the total
               the  pressure  parts  will  be  uniformly  heated  and  the  operating hours and another has one third of the total
               boiler will come on line quickly without danger of stress  operating hours. The boiler with the most operating
               cracking.                                            hours will experience problems giving you a good in-
                    Now, quit heating up a boiler to maintain a stand-  dication when to maintain, rebuild, or replace parts to
               by. It wastes fuel, it increases environmental pollution,  ensure the problems aren’t repeated on the other two.
               it’s bad for the equipment, and it’s a waste of your time.  You’ll also have two boilers with less wear than one and
                    I’ve discovered that plants which seem enamored  one with less wear than the other two. If you only have
               with the concept of standby boilers also like to rotate  two boilers one should have twice as many hours as the
               them frequently. They’re kept on standby so it’s easier to  other.
               rotate them. There’s also a bit of confusion regarding the     Another perpetuated bit of foolishness is alternat-
               status of a boiler on standby that should be cleared up;  ing systems that are constantly switching boilers. Either
               it seems to happen frequently in plants with multiple  each time a boiler cycles or every day. Heating up a
               heating boilers. Just because the pressure gauge shows  boiler takes energy and switching to another results in
               the same pressure as operating boilers doesn’t mean the  all that energy being lost. Why waste it every day? If one
               boiler is hot. Steam from the operating boilers will flow  boiler is too big for the load (it is cycling) why would
               to an idle boiler. A power boiler with a leaking non-  you operate two to double radiation losses? Rotate the
               return valve can hold a head of steam.               boilers on at least a quarterly schedule so they get at
                    The problem is that pressure and temperature is  least three month’s rest before you start them up again.
               only above the water line; everything below can be dead  Start-ups always put a strain on a boiler, why strain
               cold, and in one case was actually freezing. For the same  them any more frequently than necessary?
               reasons that water circulates in a boiler when it’s firing     Oh, that’s right, you would have to lay up the boil-
               it will stagnate when it isn’t. I commonly come across  er properly if you didn’t use it regularly. Collect some
               boilers that show pressure where I can reach down and  data, do a little math and you’ll discover that it’s costing
               touch the bottom drum or a portion of the shell and find  the owner a considerable amount of money to keep two
               it cold. A boiler in that situation is not a hot standby, it’s  boilers running when one is adequate. Lay one up for a
               a bunch of thermally distorted steel. Any rapid changes  summer, or a year. The little bit of work it takes to do the
               in the water level can result in stress cracking of the  job right will pay off in lower fuel bills that you can take
               drum or shell and tube sheets.                       credit for.
                    Systems that simply drain the condensate off at the
               surface of these boilers maintains an artificial state that
               is dangerous. Those boilers should either be allowed to  BOTTOM BLOWOFF
               flood, so they’re all cold, with the condensate removed
               in a section of piping above the boiler, or isolated and     Some of you will argue this point because you’ve
               put in lay up properly. It’s not too expensive to replace a  used it for everything, everything  but the only pur-
               piece of piping compared to replacing a boiler.      pose for bottom blowoff. Its only purpose is to remove
                                                                    sludge, scale, and sediment that collects in the bottom
                                                                    drum of the boiler. There is a prescribed procedure for it
               ROTATING BOILERS                                     with some variations depending on the type of bottom
                                                                    blowoff valves that are on the boiler. Some of my cus-
                    The act of rotating boilers, sometimes called alter-  tomers don’t perform a bottom blowoff… ever. That’s
               nating although I prefer that label be used to refer to au-  because their water pretreatment and chemistry meth-
               tomatic rotation, is the operation of boilers in a manner  ods don’t create any accumulation in that bottom drum
               that assures that all the boilers have the same amount of  and the little bit that does collect is removed with each
               operating time. It has been common practice and many  cleaning for annual inspection.
               facilities have alternating controls that ensure every     Yes, you may open the bottom blowoff valves to
               boiler take its turn at operating. Why is it so important  drain the boiler for its annual internal inspection (bian-
               to make certain that all the boilers have an equal amount  nual for some of you) but draining the boiler is not the
               of use to improve the certainty that they all start having  same as performing a bottom blow. Other reasons for
               break downs at the same time?                        opening those valves are simply not acceptable. The bot-