Boiler Plant Operations                                                                              83


               generate electric power so you better know the impor-  temperature after you get the trip valve opened back up.
               tant  requirements  of  superheater  operation.  The  first     If your plant makes it a practice to lift check the
               and foremost rule is the superheater has to have steam  safety valves then do so with caution, waiting until the
               flowing through it to absorb the heat getting to the tubes  boiler has settled down after lifting each drum safety.
               or the tubes will overheat and fail. Water in superheater     Open the superheater vent first before starting to
               tubes doesn’t help, it can block flow in some tubes to  take a boiler off line, that’s first before anything else. If
               permit them overheating or suddenly blow over at high  other boilers are serving the load any reheater will have
               velocities to create water hammer damage.            to be set up to maintain steam flow as well. Whenever
                    The following guidelines should ensure proper  possible keep serving the load after shutting off the fires
               start-up of a superheated boiler. Note that some boilers,  to keep the flow up, allow the turbine to drop off with
               HRSGs in particular, can have special requirements so  the boiler so you maintain maximum possible super-
               be sure to read that instruction manual. When the boiler  heater steam flow. Don’t open the other vents and drains
               is equipped with a reheater you should have to adjust  until the boiler is down to 25 psig when you’re ready to
               valving to direct steam from the boiler through the re-  open the drum vent. There are so many variables in su-
               heater and open the reheater vents and drains. When  perheater and reheater design today that I can’t begin to
               starting up a boiler with a superheater make sure all  ensure you these procedures are the best for your plant.
               vents and drains on the superheater are open. Similarly,  Be certain you follow manufacturer’s instructions.
               check that all reheater vents and drains are open.       Some superheaters are equipped with gas bypass
                    As soon as a reasonable flow of steam is evident  dampers inside the boiler so you can control the su-
               at the boiler vent, close it to develop maximum flow  perheat temperature to a degree. Others will have an
               through the superheater. When superheater drains  intermediate desuperheater that injects feedwater into
               appear to be blowing clear with no moisture present  piping connecting two sections of a superheater to drop
               (a slight gap between the pipe and the cloud of water  the temperature coming out of the first stage and you
               droplets) close down on the drain valves to increase  may find desuperheaters on reheaters. Some of these
               flow  through  the  whole  superheater.  Similarly  choke  devices can produce a false sense of security by produc-
               down on any intermediate vents. Constantly observe  ing safe superheat readings at the boiler outlets but the
               the superheater outlet temperature, paying close atten-  temperatures upstream of the desuperheaters or in parts
               tion after any change in firing rate, number of burners or  of a superheater that aren’t affected by the dampers go
               ignitors in service, and other activities that can change  too high. In any kind of upset operating condition check
               flue  gas  flow  past  the  superheater.  Close  drains  and  as many temperatures as you can and don’t bet on the
               vents except for the final superheater vent valve once  lowest reading being the right one, always figure the
               you have the turbine rolling over. Close the superheater  highest reading is the right one.
               vent valves after the turbine is carrying a load. Close the     Desuperheaters are used to increase the supply of
               bypass valve to the reheater as well, confirming reheater  desuperheated steam (the added water evaporates and
               flow from and to the turbine before closing the reheater  becomes part of the steam). When the steam is used in
               vent valve.                                          heat exchangers and similar apparatus desuperheating
                    During operation note the superheater, and re-  reduces the amount of heating surface required in the
               heater if equipped, outlet temperature on a regular  heat exchanger. They should always leave a little super-
               basis. There are many things that can go wrong to pro-  heat in the steam so you know there’s no water racing
               duce a problem with overheating the superheater or re-  down the piping looking for an elbow to run into. When
               heater that aren’t necessarily going to be associated with  you’re operating a superheated steam plant you have to
               changes in sound. If the turbine trips, open the super-  know what the saturation conditions are for every ser-
               heater vent valve before trying to reset the turbine trip  vice and what are the maximum temperature ratings of
               valve. If the boiler has a reheater establish flow through  the equipment and piping.
               it as well.
                    Fooling around with a trip valve without super-
               heater flow is dangerous. There’s no steam flow so the  SWITCHING FUELS
               superheater outlet temperature indication will fall even
               though the metal a few feet inside the boiler is overheat-     Any boiler plant of a reasonable size should be
               ing. It’s very embarrassing and quite scary to see the  capable of burning more that one fuel. It provides the
               superheater outlet indication peak well above design  owner or user with an alternative fuel in the event the