Page 95 - Boiler_Operators_Handbook,_Second_Edition
P. 95

80                                                                                Boiler Operator’s Handbook


               IDLE SYSTEMS                                         panel and control panels so the indicating lights, trans-
                                                                    formers and the like keep the enclosures dry. Alterna-
                    For some strange reason people think a boiler plant  tively you should check for operation of panel heaters
               that’s shut down during the summer or an air condition-  or temporary lights installed for that purpose. You can’t
               ing system that’s shut down during the winter doesn’t  be certain that there’s sufficient power to keep the pan-
               need any attention. The contrary is true, they need more  els dry so simply open the panels once a week to check
               attention because it’s during those periods when the  for condensation; any rusting or discoloration says you
               equipment isn’t operating that they normally incur the  need heaters in them.
               most damage. Before you say I don’t know what I’m        You don’t want to discover your boiler is full of
               talking about consider this: most of the rusting and cor-  holes when you try to start it up in the fall so, if the boil-
               rosion in heating systems occurs during the summer  ers are in wet layup the water should be tested for sulfite
               when the boilers are shut down and a typical reason for  content and pH weekly and corrected if the analysis
               catastrophic failure of a chilled water system is freezing  shows the levels to be inadequate for proper storage.
               when it’s shut down. Idle equipment deserves just as  Boilers without stack caps should have the stacks cov-
               much attention as operating equipment.               ered if they are above the boiler and stack base access
                    Idle boilers should be warm (see the section on  doors opened if they aren’t so you can be certain rain
               standby boilers) or laid up wet or dry. Concerns with  isn’t entering the boiler and corroding it. Sometimes that
               warm boilers include checking to ensure they’re really  isn’t easy to do so it’s more important to see to it that
               warm; the temperature of the water at the bottom of the  any rain that falls drys out quickly by providing, and
               boiler should be the same as the water at the top of the  regularly confirming, good ventilation over the metal
               boiler. Boilers that are not up to operating pressures and  surfaces and up the stack.
               temperatures can weep enough to promote high rates of     During the winter an idle boiler can freeze up if
               localized corrosion so casing drains should be checked  the plant is sealed so much that combustion air from
               daily to ensure there’s no evidence of the boiler weeping  operating equipment is drawn down the stack of the
               excessively.                                         idle boiler. That’s why I say stack temperatures should
                    Idle boilers require more attention because an  always be recorded, even on idle boilers. Stagnant water
               operating boiler is generating inert gas; it’s less likely  piping and the like can also freeze if the cold outside air
               to explode than an idle boiler. The fuel oil and gas sup-  that’s always drawn into a boiler plant for combustion
               ply shut-off valves should be checked to ensure they’re  happens to flow over that piping or equipment.
               closed and supply pressures after them down to zero.     Chillers, cooling towers, and other air condition-
               Gas fired boilers should be checked by sniffing at an ob-  ing equipment plus any equipment or piping system
               servation port or other sampling means to ensure there  that contains water should be drained completely when
               isn’t any gas leaking into the boiler.               it’s idle. If it’s not possible to drain a system completely
                    The most expensive industrial accident incurred  then it should be filled with an antifreeze solution that’s
               to date was the result of gas igniting after leaking into  guaranteed to prevent freezing at the lowest known
               an idle boiler at the River Rouge Steel Mill in February  temperature at your plant. If neither of those options
               of 1999. The result of that boiler explosion was six dead,  are available to you then you have to be concerned with
               several injured and over a billion dollars in damage. If  freeze protection, checking every piece of idle equip-
               the boiler is oil fired the oil burner should be removed  ment regularly during the winter months to be certain
               or the oil supply piping disconnected from the burner  it’s not freezing.
               and plugged so no oil can leak into the furnace. Separate     Some freezing is due to us engineers, I’ll admit.
               ignitor gas supplies should also be isolated and checked.  I recall one installation where the engineer designed
                    The  ash pits, bunkers and  furnaces of coal  and  louvers for combustion air in the wall of a boiler room
               solid fuel fired boilers should be checked for accumula-  where the air drawn in traveled right over the chiller;
               tion of anything that could create problems including  since it was inside the boiler room it was supposed to
               water, trash, rodents and sleeping contractor employees.  be warm and plant personnel failed to drain it. At the
               Speaking of contractors, an idle boiler should be covered  beginning of the cooling season they got an expensive
               to prevent damage from contractor operations above  surprise. Remember that story because you can’t forget
               and around it and panels and fan inlets should be sealed  that standing water in the boiler plant can freeze if cold
               to keep construction dust from entering them.        air is drawn over it, including water in idle boilers.
                    I  like  to  leave  power on  a  burner management     Your water supply piping is susceptible to freezing