Page 164 - Boiler_Operators_Handbook,_Second_Edition
P. 164

Refrigeration & AC                                                                                  149

               of the evaporator to help cool the liquid refrigerant.  cooler to overcome that differential. If the pressure
               The cool gas is simply superheated a little more as it  drop in the liquid refrigerant tubing introduced an-
               absorbs the heat from the liquid. It’s also possible to  other 15 psi the combination would approach the nor-
               have an independent subcooler to cool the liquid re-  mal design of 10° subcooling. Then I would remember
               frigerant.                                           that since the liquid line ran up the building on the
                    Subcooling is necessary to ensure the liquid re-  inside it would be cooled by the conditioned room
               mains a liquid until it has exited the throttling device.  temperature. That might not help in a taller building.
               If the liquid is not subcooled sufficiently it can breach
               saturation conditions as the pressure in the liquid  Measuring superheat and subcooling
               tubing drops due to friction or changes in elevation.     Unlike our boiler plants refrigeration systems do
               When that happens small bubbles of refrigerant vapor  not always have pressure gauges and thermometers
               form in the liquid line and, because the vapor uses up  mounted in the piping. When there are gauges or ther-
               more space than liquid, result in increased velocity in  mometers it’s an indication that the reading should be
               the liquid line for more pressure drop and generation  monitored and logged regularly. Usually a set of por-
               of more vapor.                                       table gauges, called a refrigeration gauge set as shown
                    For several years, while my wife Sue served on  in Figure 5-3 and a clip on thermometer are used to
               our County Council, we attended a Maryland Asso-     determine superheat and sub-cooling. The gauge set
               ciation of Counties conference in Ocean City Mary-   in your facility will normally have the saturation tem-
               land. We stayed in a condominium on the Bayside of  peratures printed on the gauge face along with the
               the island adjacent to the convention center. The con-  pressure indication. If the temperature is not indicat-
               do’s heating and air-conditioning consisted of heat  ed on the gauge set then you will need a refrigerant
               pumps for the individual units scattered around on  card like the one shown Figure 5-4. Most of those cards
               the ground just outside the condominium deck. Each  list several refrigerants so you don’t have to carry a
               year I wondered how well those units worked for the  lot of them, only remember to use the right column.
               condos on the third floor. The change in elevation  The  gauge  set  has  three  hoses  connected  and  termi-
               (about 30 feet) would reduce the pressure in the liquid  nating in special fittings that match fittings provided
               line by almost 15 psi (density of liquid R-22 being ap-  for their connection on the refrigeration equipment.
               proximately 71.8 pounds per cubic foot at 96°F) which  Sometimes, but not always, the fittings are keyed so
               would require the refrigerant liquid to be at least 6°  that they cannot be connected improperly. The color
                                                                    of the hoses is always a key to how they should be
                                                                    connected. The blue hose fitting gets connected to the
                                                                    vapor line at the outlet of the evaporator and the red
                                                                    hose is connected to the hot line somewhere between
                                                                    the compressor and the condenser. Those hoses lead
                                                                    to the gauges to provide an indication of pressure and
                                                                    the  corresponding saturation  temperature  of the  re-
                                                                    frigerant at the point where the hose fitting is con-
                                                                    nected. The third hose, typically yellow, the one in the
                                                                    middle, is separated from the other two by the valves
                                                                    and is typically used for a connection to a bottle of
                                                                    refrigerant. That hose is used to add refrigerant to, or
                                                                    remove refrigerant from, the system. The color of that
                                                                    hose can be keyed to the refrigerant. Gauge sets exist
                                                                    that can only be used for specific refrigerants; R134a is
                                                                    one. Their fittings will also be specific matches to pre-
                                                                    vent contamination of a refrigerant system by a dif-
                                                                    ferent refrigerant. The clip on thermometer should be
                                                                    clipped onto the refrigerant piping as close as possible
                                                                    to the pressure gauge connection so a true superheat,
                                                                    the difference between saturation and actual tempera-
                                                                    ture, can be determined.
                              Figure 5-3. Gauge set
   159   160   161   162   163   164   165   166   167   168   169