Page 229 - Boiler_Operators_Handbook,_Second_Edition
P. 229

214                                                                               Boiler Operator’s Handbook


               to open the circuit breakers in addition to disconnects  sure until it exploded.
               when servicing equipment so add them to your lock-out     To ensure that can’t happen again all control cir-
               tag-out procedures.                                  cuits must have one leg grounded and all final devices
                    Maintaining grounds is a constant problem in  (control relays and fuel safety shut-off valves) have one
               many plants and I always rely on the eyes and skill of  side connected to the grounded conductor. (A grounded
               operators to spot problems before they become serious.  conductor is a wire for carrying current that is connected
               A common way to ensure a good electrical connection  to ground at one point to ensure its electrical potential
               between steel building structures and the ground is  is the same as ground) Any ground that forms in the
               installation of a grounding grid and bonding. A ground-  control circuit should produce a fault that will trip the
               ing grid is a pattern of copper rods laid out in the  fuse or circuit breaker. If that doesn’t happen the ground
               ground around and under a building to provide good  should produce a short circuit between the fault and
               contact with the earth, they are welded or mechanically  ground so there is no voltage across the associated re-
               attached to each other and to bonding jumpers that ex-  lays or safety shut-off valves to keep them open.
               tend to the building structure.                          Of course, if the conduit or other parts located
                    Bonding is the process of installing jumpers con-  where the wiring insulation fails is not grounded it not
               necting one piece of metal to another to ensure electri-  only becomes a point of high potential that can cause
               cal current can flow from one to the other. If buildings  personnel injury. It’s also a conductor that can bypass
               were not grounded lightning could create thousands of  some of the limit switches on the boiler. To ensure there
               volts of potential between the building and ground, let  are no inadequately grounded metals around a boiler
               alone the static electricity differences in a building from  an annual check should be made of their resistance to
               a cloud passing over it. If you touched the building with  ground. Using a simple multi-meter set at the lowest re-
               your feet in contact with the ground, well… you would  sistance setting and one very long test lead check the re-
               become the grounding conductor.                      sistance between the grounded conductor in the burner
                    Look  around  at  the  bases  of  steel  columns  and  management panel and every metal object (except wir-
               you’ll see an occasional wire run up through the con-  ing) on and around the boiler. The resistance should be
               crete to an attachment on the steel, that’s a bonding  less than 5 ohms everywhere. Usually you will find the
               jumper. The connections can be mechanical or the metals  resistance is less than one ohm with 0.3 to 0.5 being com-
               can be fused using a thermite welding process. Thermite  mon. I chose 5 ohms because a little more resistance can
               welding creates a puddle of hot molten metal that at-  produce enough potential to keep a small control relay
               taches itself to the steel and wiring. The bonding wires  energized.
               serve as the bonding jumpers because there’s no guar-     Just like you check motors for overheating bear-
               antee that the anchor bolts, nuts, and column bases will  ings, you should check out your electrical panels and
               maintain electrical continuity.                      switchgear for loose connections that generate heat.
                    The problem with those connections is they are  The wiring can loosen especially when the equipment
               exposed and can be broken loose by any number of  is started and stopped frequently because the wire does
               methods. Your effort should simply consist of noting  heat up a little bit every time it runs and that results in
               any damage to one and repairing it or having it repaired  expansion and contraction of the metal that can loosen
               immediately. Caution is advisable because there could  the connections.
               be a voltage difference between the two so always make     Loose connections are very common with alumi-
               certain you have no voltage difference before attempt-  num wiring because aluminum has a larger coefficient
               ing to restore a connection and be aware that any num-  of expansion than copper. During a normal round you
               ber of incidences in and around the facility could create  just lay your hand on the front of each panel and com-
               a difference, including a cloud passing over.        pare what you feel to previous rounds. With large panels
                    I’m particularly concerned with grounds in and  it’s a good idea to sweep your hand over the front to
               around boiler systems because we’re dealing with so  note hot spots which are indicators of loose connections.
               much steel and water, all good conductors of electricity  If you detect one plan to shut down that equipment to
               (well water normally is) and lack of a ground invites  correct the problem… before the equipment picks its
               problems with control operation. The deadly explosion  own time to go down!
               of a boiler at the New York Telephone Company in 1963     Prior to annual inspections you should perform
               was associated with ground paths bypassing some limit  a detailed examination for hot spots at connections,
               switches so the boiler continued to fire and build pres-  opening panels whenever possible and scanning all
   224   225   226   227   228   229   230   231   232   233   234