Page 260 - Boiler_Operators_Handbook,_Second_Edition
P. 260

Water Treatment                                                                                     245


               down piping it must come from a section that’s almost  or heat up the cooling water side of the cooler to blow it.
               the same pressure as in the boiler. If it’s drawn after the  It’s also almost impossible to dilute a water sample with
               water pressure drops and some of it flashes to steam  cooling water.
               you have no assurance that your sample is representa-     Close the water supply and sample outlet valves
               tive. It could be the water left after the steam flashes off   to shut down the cooler. When ready to draw a sample
               and contain higher concentrations of solutes (the stuff   you first check the cooling water drain to be certain the
               dissolved in it, including your treatment chemicals) or  cooler isn’t leaking then open the cooling water supply.
               it could be condensed flash steam and contain almost  Once cooling water is flowing open the sample outlet
               none of the solutes. If you’re trying to draw a sample off   valve to flush the sample piping and get a fresh sample
               the blowoff piping or any other volume where the water  up to the cooler. Boiler water and deaerated feedwater
               is stagnant you’re not getting a representative sample.  should start flashing at the outlet so you know you have
               The best point to draw a sample from is the continuous  a fresh sample. Throttle the sampling outlet valve until
               blowdown piping before the water passes through any  you get a reasonable flow of cooled water.
               orifice or throttling valve.                             To ensure there’s no vapor vented off your sample,
                    When I see someone put on chemical prepara-     or condensate from the air getting in, the sample should
               tion gear and try grabbing a sample off the blowdown  be cooled to the same temperature as the air in that area.
               valve at the base of the water column I know it’s not a  A thermometer sensing the water temperature leaving
               representative sample. Samples of raw water, softened  the cooler (Figure 8-1) works well but it has to be able to
               water, etc., can be collected by simply draining water  take the maximum possible temperature of the sample,
               from the systems and making certain the sampling pip-  the temperature in the boiler. The thermometer is also
               ing is flushed so the sample is fresh and representative  suggested to be certain you don’t burn your fingers
               of the water flowing through the system. Samples of  when drawing the sample.
               boiler feedwater, hydronic system water, boiler water,     Once a sample is flowing you should rinse all the
               and most condensate require cooling to ensure you get a  apparatus that will be contacting the sample so previ-
               representative sample.                               ous samples don’t contaminate what you’re analyzing.
                    Sample coolers can be as simple as a large coil of  If you must draw a sample from a location away from
               copper tubing, to allow air cooling of a low pressure  the test bench always draw enough to rinse the testing
               boiler water sample, to units designed for operating
               pressures up to 5,000 psi. You should read the instruc-
               tions for your sample cooler and follow them, but when
               they’re lacking, the following guidelines are suggested.
                    A sample cooler should be shut down except when
               it is used to draw a sample. To ensure there’s no vacuum
               created in it to draw air in and corrode it and no way to
               over-pressure it through thermal expansion leaving it
               under pressure is recommended. That means its cooling
               water and sample outlet valves should be closed, right?
               Well, that’s fine as long as it isn’t leaking and you’ll
               never know when it springs a leak under those condi-
               tions until the cooling water system is contaminated
               with boiler water. I like to connect a sample cooler so
               there’s only a cooling water supply valve and the cool-
               ing water outlet is piped to form a loop up above the
               cooler, vented, then dropped to a drain. The loop keeps
               the cooler under static pressure so air can’t get in and
               will allow for expansion of the water and even gener-
               ated steam to escape if someone opens the sample line
               first. If the cooler leaks the boiler water will go to drain,
               not back into the cooling water system. There’s no way
               some dummy can close an outlet valve that isn’t there to
               force leaking boiler water into the cooling water system       Figure 8-1. Water sample cooler
   255   256   257   258   259   260   261   262   263   264   265